Define how many info/data frames the device is allowed to send while holding the token.
Table 205: Range:
Min: 1
Max: 65534
Default value: 1
8-74 "I am" Service
Default value: [0] Send at power-up
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: True
Table 206: Option:
[0] Send at power-up Select when the device should send the
I am service
message only at power-up.
[1] Continuously
Select when the device should send the
I am service
message continuously with an interval of approxi-
mately 1 minute.
8-75 Intialisation Password
Default value: admin
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: VisibleString
Change during operation: True
Enter the password needed for execution of Drive Re-initialization from BACnet.
Table 207: Range:
Min: 1
Max: 1
Default value: admin
8-79 Protocol Firmware version
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: -2
Data type: u_int16
Change during operation: False
Firmware revision of the drive is in index 0, Modbus is in index 1, Metasys N2 is in index 2, FLN is in index 3, BACnet is in index 4.
Table 208: Range:
Min: 0
Max: 655
Default value: 0
4.9.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the bus communication via the FC port.
8-80 Bus Message Count
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
This parameter shows the number of valid telegrams detected on the bus.
Table 209: Range:
Min: 0
Max: 4294967295
Default value: 0
8-81 Bus Error Count
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: 0
Data type: u_int32
Change during operation: True
This parameter shows the number of telegrams with faults (for example, CRC fault), detected on the bus.