0-44 [Off/Reset] Key on LCP
Default value: [1] Enabled
Parameter type: Option
2-setup: All setups
Conversion index: -
Data type: u_int8
Change during operation: True
Table 31: Option:
[0]
Disabled
Disable the [Off/Reset] key.
[1]
Enabled
Enable both off and reset functions.
[7]
Enable Reset Only
Enable the reset function, and disable the off function to avoid unintended stop of the drive.
4.2.5 0-5* Copy/Save
Copy parameter settings between setups and to/from the LCP.
0-50 LCP Copy
Default value: [0] No copy
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Table 32: Option:
[0]
No copy
No action.
[1]
All to LCP
Copy all parameters in all setups from the drive memory to the LCP memory. For service purposes,
copy all parameters to the LCP after commissioning.
[2]
All from LCP
Copy all parameters in all setups from the LCP memory to the drive memory.
[3]
Size indep. from
LCP
Copy only the parameters that are independent of the motor size. The latter selection can be used to
program several drives with the same function without disturbing motor data that is already set.
[10] Delete LCP copy
data
Delete copied parameters in LCP. This function requires that LCP version is greater than or equal to
V11.00.
0-51 Set-up Copy
Default value: [0] No copy
Parameter type: Option
2-setup: 1 setup
Conversion index: -
Data type: u_int8
Change during operation: False
Table 33: Option:
[0] No copy
No action.
[1] Copy from setup 1
Copy from setup 1 to setup 2.
[2] Copy from setup 2
Copy from setup 2 to setup 1.
[9] Copy from factory setup
Copy factory setting to programming setup (selected in
parameter 0-11 Programming Set-up
).
4.2.6 0-6* Password
This parameter group defines password to access menus.
0-60 Main Menu Password
Default value: 0
Parameter type: Range
2-setup: 1 setup
Conversion index: -
Data type: u_int16
Change during operation: True
Define the password for access to the Main Menu via the [Main Menu] key. Setting the value to 0 disables the password function.
This parameter hides after a password is defined.