Digital input function
Select
Terminal
External interlock
[51]
DigiPot increase
[55]
All
DigiPot decrease
[56]
All
DigiPot clear
[57]
All
Digipot hoist
[58]
All
Counter A (up)
[60]
29, 33
Counter A (down)
[61]
29, 33
Reset Counter A
[62]
All
Counter B (up)
[63]
29, 33
Counter B (down)
[64]
29, 33
Reset counter B
[65]
All
Mech. brake feedb.
[70]
All
Mech. brake feedb. inv.
[71]
All
PID error inv.
[72]
All
PID reset I-part
[73]
All
PID enable
[74]
All
PTC card 1
[80]
All
Profidrive OFF2
[91]
Profidrive OFF3
[92]
Start edge triggered
[98]
Safe option reset
[100]
Table 6.5 Digital Input Functions
FC 300 standard terminals are 18, 19, 27, 29, 32 and 33.
MCB 101 terminals are X30/2, X30/3 and X30/4.
Terminal 29 functions as an output only in FC 302.
Functions dedicated to only one digital input are stated in
the associated parameter.
All digital inputs can be programmed to these functions:
[0]
No
operation
No reaction to signals transmitted to the
terminal.
[1]
Reset
Resets adjustable frequency drive after a TRIP/
ALARM. Not all alarms can be reset.
[2]
Coast
inverse
(Default digital input 27): Coasting stop,
inverted input (NC). The adjustable frequency
drive leaves the motor in free mode. Logic ‘0’
⇒
coasting stop.
[3]
Coast and
reset
inverse
Reset and coasting stop Inverted input (NC).
Leaves the motor in free mode and resets the
adjustable frequency drive. Logic ‘0’
⇒
coasting
stop and reset.
[4]
Quick stop
inverse
Inverted input (NC). Generates a stop in
accordance with the quick-stop ramp time set
in
3-81 Quick Stop Ramp Time
. When motor
stops, the shaft is in free mode. Logic ‘0’
⇒
Quick stop.
[5]
DC brake
inverse
Inverted input for DC braking (NC). Stops
motor by energizing it with a DC current for a
certain time period. See
2-01 DC Brake Current
to
2-03 DC Brake Cut-in Speed [RPM]
. The
function is only active when the value in
2-02 DC Braking Time
is different from 0.
Logic ’0’
⇒
DC braking.
[6]
Stop
inverse
Stop inverted function. Generates a stop
function when the selected terminal goes from
logical level ‘1’ to ‘0’. The stop is performed
according to the selected ramp time
(
parameter 3-42 Ramp 1 Ramp-down Time
,
3-52 Ramp 2 Ramp-down Time
,
3-62 Ramp 3
Ramp-down Time
,
3-72 Ramp 4 Ramp-down
Time
).
NOTICE!
When the adjustable frequency drive is
at the torque limit and has received a
stop command, it does not always stop
by itself. To ensure that the adjustable
frequency drive stops, configure a
digital output to
[27] Torque limit & stop
and connect this digital output to a
digital input that is configured as coast.
[8]
Start
(Default digital input 18): Select start for a
start/stop command. Logic ‘1’ = start, logic ‘0’
= stop.
[9]
Latched
start
The motor starts if a pulse is applied for min. 2
ms. The motor stops when stop inverse is
activated or a reset command (via DI) is given.
[10] Reversing
(Default digital input 19). Change the direction
of motor shaft rotation. Select logic ‘1’ to
reverse. The reversing signal only changes the
direction of rotation. It does not activate the
start function. Select both directions in
4-10 Motor Speed Direction
. The function is not
active in process closed-loop.
[11] Start
reversing
Used for start/stop and for reversing on the
same wire. Signals on start are not allowed at
the same time.
[12] Enable start
forward
Disengages the counter-clockwise movement
and allows for the clockwise direction.
[13] Enable start
reverse
Disengages the clockwise movement and
allows for the counter-clockwise direction.
[14] Jog
(Default digital input 29): Use to activate jog
speed. See
[15] Preset
reference
on
Shifts between external reference and preset
reference. It is assumed that
[1] External/preset
has been selected in
3-04 Reference Function
.
Logic '0' = external reference active; logic '1' =
one of the eight preset references is active.
[16] Preset ref
bit 0
Preset ref. bit 0,1, and 2 enables a choice
between one of the eight preset references
according to
Programming
Instruction Manual
66
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
6
6
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......