6 Programming
6.1 How to Program the Adjustable
Frequency Drive
6.1.1 Quick Set-up Parameters
0-01 Language
Option:
Function:
Defines the language to be used in the
display. The adjustable frequency drive can
be delivered with four different language
packages. English and German are
included in all packages. English cannot be
erased or manipulated.
[0]
English
Part of Language packages 1 - 4
[1]
Deutsch
Part of Language packages 1 - 4
[2]
Francais
Part of Language package 1
[3]
Dansk
Part of Language package 1
[4]
Spanish
Part of Language package 1
[5]
Italiano
Part of Language package 1
Svenska
Part of Language package 1
[7]
Nederlands
Part of Language package 1
[10] Chinese
Part of Language package 2
Suomi
Part of Language package 1
[22] English US
Part of Language package 4
Greek
Part of Language package 4
Bras.port
Part of Language package 4
Slovenian
Part of Language package 3
Korean
Part of Language package 2
Japanese
Part of Language package 2
Turkish
Part of Language package 4
Trad.Chinese
Part of Language package 2
Bulgarian
Part of Language package 3
Srpski
Part of Language package 3
Romanian
Part of Language package 3
Magyar
Part of Language package 3
Czech
Part of Language package 3
0-01 Language
Option:
Function:
Polski
Part of Language package 4
Russian
Part of Language package 3
Thai
Part of Language package 2
Bahasa
Indonesia
Part of Language package 2
[52] Hrvatski
1-20 Motor Power [kW]
Range:
Function:
Size
related
*
[ 0.09 -
3000.00
kW]
Enter the nominal motor power in kW
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while
the motor is running. This parameter is
visible in LCP if
0-03 Regional Settings
is
[0] International.
NOTICE!
Four sizes down, one size up from
nominal unit rating.
1-22 Motor Voltage
Range:
Function:
Size
related
*
[ 10 -
1000 V]
Enter the nominal motor voltage
according to the motor nameplate data.
The default value corresponds to the
nominal rated output of the unit.
This parameter cannot be adjusted while
the motor is running.
1-23 Motor Frequency
Range:
Function:
Size
related
*
[20 -
1000
Hz]
Min - Max motor frequency: 20–1000 Hz.
Select the motor frequency value from the
motor nameplate data. If a value different
from 50 Hz or 60 Hz is selected, it is
necessary to adapt the load independent
settings in
1-50 Motor Magnetization at Zero
Speed
to
1-53 Model Shift Frequency
. For 87
Hz operation with 230/400 V motors, set the
nameplate data for 230 V/50 Hz. Adapt
4-13 Motor Speed High Limit [RPM]
and
parameter 3-03 Maximum Reference
to the 87
Hz application.
Programming
Instruction Manual
52
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222