WARNING/ALARM 12, Torque limit
The torque has exceeded the value in
4-16 Torque Limit
Motor Mode
or the value in
4-17 Torque Limit Generator
Mode
.
14-25 Trip Delay at Torque Limit
can change this
warning from a warning-only condition to a warning
followed by an alarm.
Troubleshooting
If the motor torque limit is exceeded during
ramp-up, extend the ramp-up time.
If the generator torque limit is exceeded during
ramp-down, extend the ramp-down time.
If torque limit occurs while running, possibly
increase the torque limit. Make sure that the
system can operate safely at a higher torque.
Check the application for excessive current draw
on the motor.
WARNING/ALARM 13, Overcurrent
The inverter peak current limit (approximately 200% of the
rated current) is exceeded. The warning lasts about 1.5 s,
then the adjustable frequency drive trips and issues an
alarm. Shock loading or quick acceleration with high inertia
loads can cause this fault. If the acceleration during ramp
up is quick, the fault can also appear after kinetic backup.
If extended mechanical brake control is selected, trip can
be reset externally.
Troubleshooting
Remove power and check if the motor shaft can
be turned.
Make sure that the motor size matches the
adjustable frequency drive.
Check parameters 1-20 to 1-25 for correct motor
data.
ALARM 14, Ground fault
There are current from the output phases to ground, either
in the cable between the adjustable frequency drive and
the motor or in the motor itself.
Troubleshooting
Remove power to the adjustable frequency drive
and repair the ground fault.
Check for ground faults in the motor by
measuring the resistance to the ground of the
motor cables and the motor with a
megohmmeter.
Perform current sensor test.
ALARM 15, Hardware mismatch
A fitted option is not operational with the present control
board hardware or software.
Record the value of the following parameters and contact
Danfoss:
15-40 FC Type
15-41 Power Section
15-42 Voltage
15-43 Software Version
15-45 Actual Typecode String
15-49 SW ID Control Card
15-50 SW ID Power Card
15-60 Option Mounted
15-61 Option SW Version
(for each option slot)
ALARM 16, Short-circuit
There is short-circuiting in the motor or motor wiring.
Remove power to the adjustable frequency drive and
repair the short circuit.
WARNING/ALARM 17, Control word timeout
There is no communication to the adjustable frequency
drive.
The warning is only active when
8-04 Control Word Timeout
Function
is not set to
[0] Off
.
If
8-04 Control Word Timeout Function
is set to
[2] Stop
and
[26] Trip
, a warning appears and the adjustable frequency
drive ramps down until it trips then displays an alarm.
Troubleshooting:
Check connections on the serial communication
cable.
Increase
8-03 Control Word Timeout Time
Check the operation of the communication
equipment.
Verify a proper installation based on EMC
requirements.
WARNING/ALARM 22, Hoist mechanical brake
Report value shows what kind it is.
0 = The torque ref. was not reached before timeout
(Parameter 2-27).
1 = Expected brake feedback not received before timeout
(Parameters 2-23, 2-25).
Warnings and Alarms
Instruction Manual
132
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
9
9
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......