5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
Function:
[70]
Logic rule 0
See parameter group
13-4* Logic
Rules
. If Logic Rule 0 in SLC is true,
the output goes high. Otherwise, it is
low.
[71]
Logic rule 1
See parameter group
13-4* Logic
Rules
. If Logic Rule 1 in SLC is true,
the output goes high. Otherwise, it is
low.
[72]
Logic rule 2
See parameter group
13-4* Logic
Rules
. If Logic Rule 2 in SLC is true,
the output goes high. Otherwise, it is
low.
[73]
Logic rule 3
See parameter group 13-4*(Smart
Logic Control). If Logic Rule 3 in SLC
is true, the output goes high.
Otherwise, it is low.
[74]
Logic rule 4
See parameter group
13-4* Logic
Rules
. If Logic Rule 4 in SLC is true,
the output goes high. Otherwise, it is
low.
[75]
Logic rule 5
See parameter group
13-4* Logic
Rules
. If Logic Rule 5 in SLC is true,
the output goes high. Otherwise, it is
low.
[80]
SL digital output A See
13-52 SL Controller Action
. Output
A is low on smart logic action
[32] Set
digital out A low
. Output A is high on
smart logic action
[38] Set digital out A
high
.
[81]
SL digital output B See
13-52 SL Controller Action
. Output
B is low on smart logic action
[33] Set
digital out B low
. Output B is high on
smart logic action
[39] Set digital out B
high
.
[82]
SL digital output C See
13-52 SL Controller Action
. Output
C is low on smart logic action
[34] Set
digital out C low
. Output C is high on
smart logic action
[40] Set digital out C
high
.
[83]
SL digital output D See
13-52 SL Controller Action
. Output
D is low on smart logic action
[35] Set
digital out D low
. Output D is high on
smart logic action
[41] Set digital out
D high
.
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB
113), Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6]
(MCB 105), Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
Function:
[84]
SL digital output E See
13-52 SL Controller Action
. Output
E is low on smart logic action
[36] Set
digital out E low
. Output E is high on
smart logic action
[42] Set digital out E
high
.
[85]
SL digital output F See
13-52 SL Controller Action
. Output
F is low on smart logic action
[37] Set
digital out F low
. Output F is high on
smart logic action
[43] Set digital out F
high
.
[120] Local ref active
Output is high when
3-13 Reference
Site
= [2] Local or when
3-13 Reference
Site
=
[0] Linked to Hand/Auto
at the
same time as the LCP is in [Hand on]
mode.
Reference site
set in
3-13 Reference
Site
Local
refer-
ence
active
[120]
Remote
reference
active
[121]
Reference site:
Local
3-13 Reference
Site
[2]
1
0
Reference site:
Remote
3-13 Reference
Site
[1]
0
1
Reference site:
Linked to Hand/
Auto
Hand
1
0
Hand
⇒
off
1
0
Auto
⇒
off
0
0
Auto
0
1
Table 6.9 Local and Remote
Reference
[121] Remote ref active
Output is high when
3-13 Reference
Site
=
[1] Remote
or
[0] Linked to
Hand/Auto
while the LCP is in [Auto
on] mode. See
.
[122] No alarm
Output is high when no alarm is
present.
Programming
Instruction Manual
74
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
6
6