3.4.19 Electrical Installation, Control
Terminals
To connect the cable to the terminal:
1.
Strip insulation by about 0.35–0.4 in [9–10 mm]
Electrical installationControl terminals
130BA150.10
9 - 10 mm
(0.37 in)
Figure 3.22 Length to Strip the Insulation
2.
Insert a screwdriver (max. 0.016x0.1 in [0.4x2.5
mm]) in the square hole.
3.
Insert the cable in the adjacent circular hole.
130B
T312.10
Figure 3.23 Inserting the Cable in the Terminal Block
4.
Remove the screwdriver. The cable is now
mounted in the terminal.
To remove the cable from the terminal:
1.
Insert a screwdriver (max. 0.016x0.1 in [0.4x2.5
mm]) in the square hole.
2.
Pull out the cable.
130B
T311.10
Figure 3.24 Removing the Screwdriver after Cable Insertion
130B
T306.10
Figure 3.25 Control Terminal Locations
Installation
Instruction Manual
MG37A222
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
33
3
3