[30]
Brake fault
(IGBT)
Output is logic ‘1’ when the brake IGBT is
short-circuited. Use this function to protect
the adjustable frequency drive if there is a
fault on the brake modules. Use the
output/relay to cut out the line voltage
from the adjustable frequency drive.
[31]
Relay 123
Relay is activated when control word [0] is
selected in parameter group
8-**
Communications and Options
.
[32]
Mechanical
brake control
Enables control of an external mechanical
brake, see description in
[33]
Safe stop
activated (FC
302 only)
Indicates that the safe stop on terminal 37
has been activated.
[40]
Out of ref
range
Active when the actual speed is outside
settings in
4-52 Warning Speed Low
to
4-55 Warning Reference High
.
[41]
Below
reference low
Active when actual speed is below speed
reference setting.
[42]
Above
reference high
Active when actual speed is above speed
reference setting
[43]
Extended PID
Limit
[45]
Bus Ctrl
Controls output via bus. The state of the
output is set in
5-90 Digital & Relay Bus
Control
. The output state is retained in the
event of bus timeout.
[46]
Bus Ctrl On at
timeout
Controls output via bus. The state of the
output is set in
5-90 Digital & Relay Bus
Control
. If bus timeout, the output state is
set high (On).
[47]
Bus Ctrl Off at
timeout
Controls output via bus. The state of the
output is set in
5-90 Digital & Relay Bus
Control
. If bus timeout, the output state is
set low (Off).
[51]
MCO
controlled
Active when an MCO 302 or MCO 305 is
connected. The output is controlled from
option.
[55]
Pulse output
[60]
Comparator 0
See parameter group
13-1* Comparators
. If
comparator 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61]
Comparator 1
See parameter group
13-1* Comparators
. If
comparator 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62]
Comparator 2
See parameter group
13-1* Comparators
. If
comparator 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63]
Comparator 3
See parameter group
13-1* Comparators
. If
comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64]
Comparator 4
See parameter group
13-1* Comparators
. If
comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65]
Comparator 5
See parameter group
13-1* Comparators
. If
comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70]
Logic Rule 0
See parameter group
13-4* Logic Rules
. If
logic rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71]
Logic Rule 1
See parameter group
13-4* Logic Rules
. If
logic rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72]
Logic Rule 2
See parameter group
13-4* Logic Rules
. If
logic rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73]
Logic Rule 3
See parameter group
13-4* Logic Rules
. If
logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74]
Logic Rule 4
See parameter group
13-4* Logic Rules
. If
logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75]
Logic Rule 5
See parameter group
13-4* Logic Rules
. If
logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80]
SL Digital
Output A
See
13-52 SL Controller Action
. The output
goes high whenever the smart logic action
[38] Set dig. out. A high
is executed. The
output goes low whenever the smart logic
action
[32] Set dig. out. A
low is executed.
[81]
SL Digital
Output B
See
13-52 SL Controller Action
. The input
goes high whenever the smart logic action
[39]
Set dig. out. A high
is executed. The
input goes low whenever the smart logic
action [33]
Set dig. out. A low
is executed.
[82]
SL Digital
Output C
See
13-52 SL Controller Action
. The input
goes high whenever the smart logic action
[40]
Set dig. out. A high
is executed. The
input goes low whenever the Smart Logic
Action [34]
Set dig. out. A low
is executed.
[83]
SL Digital
Output D
See
13-52 SL Controller Action
. The input
goes high whenever the smart logic action
[41]
Set dig. out. A
high is executed. The
input goes low whenever the smart logic
action [35]
Set dig. out. A low
is executed.
[84]
SL Digital
Output E
See
13-52 SL Controller Action
. The input
goes high whenever the smart logic action
[42]
Set dig. out. A high
is executed. The
input goes low whenever the smart logic
action [36]
Set dig. out. A low
is executed.
[85]
SL Digital
Output F
See
13-52 SL Controller Action
. The input
goes high whenever the smart logic action
[43]
Set dig. out. A high
is executed. The
input goes low whenever the smart logic
action [37]
Set dig. out. A low
is executed.
Programming
Instruction Manual
70