7.3 Connection Examples for Control of
Motor with External Signal Provider
NOTICE!
The following examples refer only to the adjustable
frequency drive control card (right LCP),
not
the filter.
7.3.1 Start/Stop
Terminal 18 =
5-10 Terminal 18 Digital Input
[8]
Start
Terminal 27 =
5-12 Terminal 27 Digital Input
[0]
No
operation
(Default
coast inverse
)
Terminal 37 = Safe stop
Figure 7.5 Start/Stop Parameters
7.3.2 Pulse Start/Stop
Terminal 18 =
5-10 Terminal 18 Digital Input
[9]
Latched
start
Terminal 27=
5-12 Terminal 27 Digital Input
[6]
Stop inverse
Terminal 37 = Safe torque off
Figure 7.6 Pulse Start/Stop Parameters
Application Examples
Instruction Manual
124
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
7
7