Bottom section
always shows the state of the adjustable frequency drive in
status mode.
Top section
Middle section
Bottom section
Status
43 RPM
1.4 Hz
Auto Remote Running
! Pwr.card temp (W29)
2.9%
5.44 A
25.3 kW
1(1)
130BP074.10
!
Figure 5.5 Bottom Section Status Mode
Display contrast adjustment
Press [status] and [
▲
] for darker display
Press [Status] and [
▼
] for brighter display
LEDs:
If certain threshold values are exceeded, the alarm and/or
warning LED lights up. A status and alarm text appear on
the control panel.
The On LED is activated when the adjustable frequency
drive receives power from:
•
AC line voltage
•
a DC bus terminal
•
an external 24 V supply
At the same time, the back light is on. LEDs
•
Green LED/On: Control section is working.
•
Yellow LED/Warn: Indicates a warning.
•
Flashing Red LED/Alarm: Indicates an alarm.
On
Warn.
Alarm
130BP044.10
Figure 5.6 LED Status Lights
GLCP keys
Menu keys
The menu keys are divided into functions. The keys below
the display and LEDs are used for parameter set-up,
including choice of display indication during normal
operation.
130BP045.10
Status
Quick
Menu
Main
Menu
Alarm
Log
Figure 5.7 Menu Keys
[Status]
Indicates the status of the adjustable frequency drive
(and/or the motor) or the filter respectively. On the drive
LCP, three different readouts can be selected by pressing
the [Status] key:
Five line readouts, four line readouts, or Smart Logic
Control.
Smart Logic Control is not available for the filter.
Use [Status] for selecting display mode or reverting to
display mode from:
•
quick menu
•
main menu
•
alarm mode
Use the [Status] key to toggle single or double readout
mode. Status
[Quick Menu]
Allows quick set-up of the adjustable frequency drive or
the filter and programming of the most common
functions. Quick menu
The [Quick Menu] consists of:
•
Q1: My Personal Menu
•
Q2: Quick Set-up
•
Q5: Changes Made
•
Q6: Loggings
Since the active filter is an integrated part of the Low
Harmonic Drive, only a minimum of programming is
necessary. The filter LCP displays information about filter
operation such as THD of voltage or current, corrected
current, injected current or Cos
ϕ
and true power factor.
The Quick Menu parameters can be accessed immediately
unless a password has been created via parameters 0–60,
0–61, 0–65 or 0–66.
It is possible to switch directly between quick menu mode
and main menu mode.
[Main Menu]
Is used for programming all parameters.
The main menu parameters can be accessed immediately
unless a password has been created via parameters 0–60,
0–61, 0–65 or 0–66.
It is possible to switch directly between main menu mode
and quick menu mode.
Parameter shortcut can be carried out by pressing down
the
[Main Menu]
key for three seconds. The parameter
shortcut allows direct access to any parameter.
User Interface
Instruction Manual
46
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
5
5