![Danfoss VLT AutomationDrive FC 302 Instruction Manual Download Page 83](http://html1.mh-extra.com/html/danfoss/vlt-automationdrive-fc-302/vlt-automationdrive-fc-302_instruction-manual_3427329083.webp)
6.3.3 1-** Load/Motor
Par.
No. #
Parameter description
Default value
4-set-up
FC 302
only
Change
during
operation
Conver-
sion index
Type
1-0* General Settings
1-00
Configuration Mode
ExpressionLimit
All set-ups
TRUE
-
Uint8
1-01
Motor Control Principle
ExpressionLimit
All set-ups
FALSE
-
Uint8
1-02
Flux Motor Feedback Source
[1] 24V encoder
All set-ups
x
FALSE
-
Uint8
1-03
Torque Characteristics
[0] Constant torque
All set-ups
TRUE
-
Uint8
1-04
Overload Mode
[0] High torque
All set-ups
FALSE
-
Uint8
1-05
Local Mode Configuration
[2] As mode par 1-00
All set-ups
TRUE
-
Uint8
1-06
Clockwise Direction
[0] Normal
All set-ups
FALSE
-
Uint8
1-07
Motor Angle Offset Adjust
[0] Manual
All set-ups
x
FALSE
-
Uint8
1-1* Special Settings
1-10
Motor Construction
[0] Asynchron
All set-ups
FALSE
-
Uint8
1-11
Motor Model
ExpressionLimit
All set-ups
x
FALSE
-
Uint8
1-14
Damping Gain
140 %
All set-ups
TRUE
0
Int16
1-15
Low Speed Filter Time Const.
ExpressionLimit
All set-ups
TRUE
-2
Uint16
1-16
High Speed Filter Time Const.
ExpressionLimit
All set-ups
TRUE
-2
Uint16
1-17
Voltage filter time const.
ExpressionLimit
All set-ups
TRUE
-3
Uint16
1-18
Min. Current at No Load
0 %
All set-ups
TRUE
0
Uint16
1-2* Motor Data
1-20
Motor Power [kW]
ExpressionLimit
All set-ups
FALSE
1
Uint32
1-21
Motor Power [HP]
ExpressionLimit
All set-ups
FALSE
-2
Uint32
1-22
Motor Voltage
ExpressionLimit
All set-ups
FALSE
0
Uint16
1-23
Motor Frequency
ExpressionLimit
All set-ups
FALSE
0
Uint16
1-24
Motor Current
ExpressionLimit
All set-ups
FALSE
-2
Uint32
1-25
Motor Nominal Speed
ExpressionLimit
All set-ups
FALSE
67
Uint16
1-26
Motor Cont. Rated Torque
ExpressionLimit
All set-ups
FALSE
-1
Uint32
1-29
Automatic Motor Adaptation (AMA)
[0] Off
All set-ups
FALSE
-
Uint8
1-3* Addl. Motor Data
1-30
Stator Resistance (Rs)
ExpressionLimit
All set-ups
FALSE
-4
Uint32
1-31
Rotor Resistance (Rr)
ExpressionLimit
All set-ups
FALSE
-4
Uint32
1-33
Stator Leakage Reactance (X1)
ExpressionLimit
All set-ups
FALSE
-4
Uint32
1-34
Rotor Leakage Reactance (X2)
ExpressionLimit
All set-ups
FALSE
-4
Uint32
1-35
Main Reactance (Xh)
ExpressionLimit
All set-ups
FALSE
-4
Uint32
1-36
Iron Loss Resistance (Rfe)
ExpressionLimit
All set-ups
FALSE
-3
Uint32
1-37
d-axis Inductance (Ld)
ExpressionLimit
All set-ups
x
FALSE
-4
Int32
1-38
q-axis Inductance (Lq)
ExpressionLimit
All set-ups
x
FALSE
-6
Int32
1-39
Motor Poles
ExpressionLimit
All set-ups
FALSE
0
Uint8
1-40
Back EMF at 1000 RPM
ExpressionLimit
All set-ups
x
FALSE
0
Uint16
1-41
Motor Angle Offset
0 N/A
All set-ups
FALSE
0
Int16
1-44
d-axis Inductance Sat. (LdSat)
ExpressionLimit
All set-ups
x
FALSE
-4
Int32
1-45
q-axis Inductance Sat. (LqSat)
ExpressionLimit
All set-ups
x
FALSE
-4
Int32
1-46
Position Detection Gain
100 %
All set-ups
TRUE
0
Uint16
1-47
Torque Calibration
ExpressionLimit
All set-ups
TRUE
-
Uint8
1-48
Inductance Sat. Point
35 %
All set-ups
x
TRUE
0
Int16
1-5* Load-Indep. Setting
1-50
Motor Magnetization at Zero Speed
100 %
All set-ups
TRUE
0
Uint16
1-51
Min Speed Normal Magnetizing [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
1-52
Min Speed Normal Magnetizing [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-53
Model Shift Frequency
ExpressionLimit
All set-ups
x
FALSE
-1
Uint16
1-54
Voltage reduction in fieldweakening
0 V
All set-ups
FALSE
0
Uint8
1-55
U/f Characteristic - U
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-56
U/f Characteristic - F
ExpressionLimit
All set-ups
TRUE
-1
Uint16
1-58
Flystart Test Pulses Current
ExpressionLimit
All set-ups
FALSE
0
Uint16
1-59
Flystart Test Pulses Frequency
ExpressionLimit
All set-ups
FALSE
0
Uint16
1-6* Load-Depend. Settg.
1-60
Low Speed Load Compensation
100 %
All set-ups
TRUE
0
Int16
1-61
High Speed Load Compensation
100 %
All set-ups
TRUE
0
Int16
1-62
Slip Compensation
ExpressionLimit
All set-ups
TRUE
0
Int16
1-63
Slip Compensation Time Constant
ExpressionLimit
All set-ups
TRUE
-2
Uint16
Programming
Instruction Manual
MG37A222
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
81
6
6
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......