4.
Press the navigation keys to scroll to parameter
group
0-0* Basic Settings
and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Operations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A
1(1)
130BP087.10
Figure 4.2 0-0* Basic Settings
5.
Press the navigation keys to scroll to
0-03 Regional Settings
and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A
1(1)
130BP088.10
Figure 4.3 0-03 Regional Settings
6.
Press the navigation keys to select
International
or
North America
as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters. See
for a complete list.)
7.
Press [Quick Menu] on the LCP.
8.
Press the navigation keys to scroll to parameter
group
Q2 Quick Set-up
.
9.
Press [OK].
130BB847.10
Q1 My Personal Menu
Q2 Quick Setup
Q5 Changes Made
Q6 Loggings
13.7% 13.0A 1(1)
Quick Menus
Figure 4.4 Q2 Quick Set-up
10.
Select language and press [OK].
130B
T772.10
Q2
0.0 Hz 0.00kW 1(1)
Motor Setup
1 - 21 Motor Power [kW]
4.0
kW
Figure 4.5 Select Language
11.
If a jumper wire is placed between control
terminals 12 and 27 leave
5-12 Terminal 27 Digital
Input
at factory default. Otherwise select
No
Operation
. For adjustable frequency drives with
an optional bypass, no jumper wire is required.
12.
parameter 3-02 Minimum Reference
13.
parameter 3-03 Maximum Reference
14.
3-41 Ramp 1 Ramp-up Time
15.
3-42 Ramp 1 Ramp-down Time
16.
3-13 Reference Site
. Linked to Hand/Auto* Local
Remote.
4.4 Local Control Test
CAUTION
MOTOR START!
Ensure that the motor, system and any attached
equipment are ready for start. It is the responsibility of
the user to ensure safe operation under any condition.
Failure to ensure that the motor, system, and any
attached equipment are ready for start could result in
personal injury or equipment damage.
NOTICE!
The [Hand On] key provides a local start command to
the adjustable frequency drive. The [Off] key provides
the stop function.
When operating in local mode, [
▲
] and [
▼
] increase and
decrease the speed output of the adjustable frequency
drive. [
◄
] and [
►
] move the display cursor in the numeric
display.
Start-up and Functional Tes...
Instruction Manual
42
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
4
4
Summary of Contents for VLT AutomationDrive FC 302