3-17 Reference Resource 3
Option:
Function:
Select the reference input to be used
for the third reference signal.
parameter 3-15 Reference Resource 1
,
parameter 3-16 Reference Resource 2
and
parameter 3-17 Reference Resource
define up to three different reference
signals. The sum of these reference
signals defines the actual reference.
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11] Local bus reference
[20] Digital pot.meter
[21] Analog input
X30-11
[22] Analog input
X30-12
[29] Analog Input X48/2
5-00 Digital I/O Mode
Option: Function:
NOTICE!
Once this parameter has been changed,
perform a power cycle to activate the
parameter.
Digital inputs and programmed digital outputs are pre-
programmable for operation either in PNP or NPN
systems.
[0] PNP Action on positive directional pulses
(↕)
. PNP systems
are pulled down to GND.
[1] NPN Action on negative directional pulses
(↕)
. NPN systems
are pulled up to +24 V, internally in the adjustable
frequency drive.
5-01 Terminal 27 Mode
Option:
Function:
NOTICE!
This parameter cannot be adjusted while the
motor is running.
[0] Input
Defines terminal 27 as a digital input.
[1] Output Defines terminal 27 as a digital output.
5-02 Terminal 29 Mode
Option:
Function:
This parameter is available for FC 302 only.
[0] Input
Defines terminal 29 as a digital input.
[1] Output
Defines terminal 29 as a digital output.
6.1.4 Digital Inputs
The digital inputs are used for selecting various functions
in the adjustable frequency drive. All digital inputs can be
set to the following functions:
Digital input function
Select
Terminal
No operation
[0]
All *term 32, 33
Reset
[1]
All
Coast inverse
[2]
All *term 27
Coast and reset inverse
[3]
All
Quick stop inverse
[4]
All
DC brake inverse
[5]
All
Stop inverse
[6]
All
Start
[8]
All *term 18
Latched start
[9]
All
Reversing
[10]
All *term 19
Start reversing
[11]
All
Enable start forward
[12]
All
Enable start reverse
[13]
All
Jog
[14]
All *term 29
Preset reference on
[15]
All
Preset ref bit 0
[16]
All
Preset ref bit 1
[17]
All
Preset ref bit 2
[18]
All
Freeze reference
[19]
All
Freeze output
[20]
All
Speed up
[21]
All
Slow
[22]
All
Set-up select bit 0
[23]
All
Set-up select bit 1
[24]
All
Precise stop inverse
[26]
18, 19
Precise start, stop
[27]
18, 19
Catch up
[28]
All
Slow-down
[29]
All
Counter input
[30]
29, 33
Pulse input edge
triggered
[31]
29, 33
Pulse input time based
[32]
29, 33
Ramp bit 0
[34]
All
Ramp bit 1
[35]
All
Latched precise start
[40]
18, 19
Latched precise stop
inverse
[41]
18, 19
Programming
Instruction Manual
MG37A222
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
65
6
6
Summary of Contents for VLT AutomationDrive FC 302
Page 2: ......