6.3.6 4-** Limits/Warnings
Par.
No. #
Parameter description
Default value
4-set-up
Change
during
operation
Conver-
sion index
Type
4-1* Motor Limits
4-10
Motor Speed Direction
ExpressionLimit
All set-ups
FALSE
-
Uint8
4-11
Motor Speed Low Limit [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-12
Motor Speed Low Limit [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-13
Motor Speed High Limit [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-14
Motor Speed High Limit [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-16
Torque Limit Motor Mode
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-17
Torque Limit Generator Mode
100 %
All set-ups
TRUE
-1
Uint16
4-18
Current Limit
ExpressionLimit
All set-ups
TRUE
-1
Uint32
4-19
Max Output Frequency
ExpressionLimit
All set-ups
FALSE
-1
Uint16
4-2* Limit Factors
4-20
Torque Limit Factor Source
[0] No function
All set-ups
TRUE
-
Uint8
4-21
Speed Limit Factor Source
[0] No function
All set-ups
TRUE
-
Uint8
4-3* Motor Speed Mon.
4-30
Motor Feedback Loss Function
[2] Trip
All set-ups
TRUE
-
Uint8
4-31
Motor Feedback Speed Error
300 RPM
All set-ups
TRUE
67
Uint16
4-32
Motor Feedback Loss Timeout
0.05 s
All set-ups
TRUE
-2
Uint16
4-34
Tracking Error Function
ExpressionLimit
All set-ups
TRUE
-
Uint8
4-35
Tracking Error
10 RPM
All set-ups
TRUE
67
Uint16
4-36
Tracking Error Timeout
1 s
All set-ups
TRUE
-2
Uint16
4-37
Tracking Error Ramping
100 RPM
All set-ups
TRUE
67
Uint16
4-38
Tracking Error Ramping Timeout
1 s
All set-ups
TRUE
-2
Uint16
4-39
Tracking Error After Ramping Timeout
5 s
All set-ups
TRUE
-2
Uint16
4-5* Adj. Warnings
4-50
Warning Current Low
0 A
All set-ups
TRUE
-2
Uint32
4-51
Warning Current High
ImaxVLT (P1637)
All set-ups
TRUE
-2
Uint32
4-52
Warning Speed Low
0 RPM
All set-ups
TRUE
67
Uint16
4-53
Warning Speed High
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-54
Warning Reference Low
-999999.999 N/A
All set-ups
TRUE
-3
Int32
4-55
Warning Reference High
999999.999 N/A
All set-ups
TRUE
-3
Int32
4-56
Warning Feedback Low
-999999.999 ReferenceFeed-
backUnit
All set-ups
TRUE
-3
Int32
4-57
Warning Feedback High
999999.999 ReferenceFeed-
backUnit
All set-ups
TRUE
-3
Int32
4-58
Missing Motor Phase Function
ExpressionLimit
All set-ups
TRUE
-
Uint8
4-6* Speed Bypass
4-60
Bypass Speed From [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-61
Bypass Speed From [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
4-62
Bypass Speed to [RPM]
ExpressionLimit
All set-ups
TRUE
67
Uint16
4-63
Bypass Speed To [Hz]
ExpressionLimit
All set-ups
TRUE
-1
Uint16
Programming
Instruction Manual
86
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
MG37A222
6
6