5.1.6 Changing Data Values, Step-by-Step
Certain parameters can be changed step-by-step or
infinitely variably. This method applies to
1-20 Motor Power
[kW]
,
, and
1-23 Motor
Frequency
.
The parameters are changed both as a group of numeric
data values, and as numeric data values using an infinite
number of variables.
5.1.7 Readout and Programming of
Indexed Parameters
Parameters are indexed when placed in a rolling stack.
15-30 Alarm Log: Error Code
to
15-32 Alarm Log: Time
contain a fault log which can be read out. Select a
parameter, press [OK], and use the up/down navigation
keys to scroll through the value log.
Use
3-10 Preset Reference
as another example:
Select the parameter, press [OK], and press [
▲
]/[
▼
] to scroll
through the indexed values. To change the parameter
value, select the indexed value and press [OK]. Change the
value by using [
▲
]/[
▼
]. Press [OK] to accept the new
setting. Press [Cancel] to abort. Press [Back] to leave the
parameter.
5.1.8 Quick Transfer of Parameter Settings
when Using GLCP
Once the set-up is complete, store (back up) the parameter
settings in the GLCP or on a PC via MCT 10 Set-up
software tool.
WARNING
Stop the motor before performing any of these
operations.
Data storage in LCP
1.
Go to
0-50 LCP Copy
2.
Press [OK]
3.
Select
[1] All to LCP
4.
Press [OK]
All the parameter settings are now stored in the GLCP as
indicated by the progress bar. When 100% is reached,
press [OK].
The GLCP can now be connected to another adjustable
frequency drive, and the parameter settings can be copied
to this adjustable frequency drive.
Data transfer from LCP to adjustable frequency drive
1.
Go to
0-50 LCP Copy
2.
Press [OK]
3.
Select
[2] All from LCP
4.
Press [OK]
The parameter settings stored in the GLCP are now
transferred to the adjustable frequency drive, as indicated
by the progress bar. When 100% is reached, press [OK].
5.1.9 Initialization to Default Settings
There are two ways to initialize the adjustable frequency
drive to default: Recommended initialization and manual
initialization.
Each method has a different impact. InitializationDefault
settings
5.1.9.1 Recommended Initialization Method
Initialization via
14-22 Operation Mode
)
1.
Select
14-22 Operation Mode
2.
Press [OK]
3.
Select
Initialization
(for NLCP select “2”)
4.
Press [OK]
5.
Remove power to the unit and wait for the
display to turn off.
6.
Reconnect power to reset the adjustable
frequency drive.
7.
Press [Reset]
14-22 Operation Mode
initializes all except:
Parameter 14-50 RFI 1
8-30 Protocol
8-31 Address
8-32 Baud Rate
8-35 Minimum Response Delay
8-36 Max Response Delay
8-37 Maximum Inter-Char Delay
15-00 Operating hours
to
15-05 Over Volts
15-20 Historic Log: Event
to
15-22 Historic Log: Time
15-30 Alarm Log: Error Code
to
15-32 Alarm Log: Time
NOTICE!
Parameters selected in
0-25 My Personal Menu
, stays
present, with default factory setting.
User Interface
Instruction Manual
MG37A222
Danfoss A/S © Rev. 2014-02-07 All rights reserved.
49
5
5