3-10 Preset Reference
Array [8]
Range: 0–7
Range:
Function:
0 %
*
[-100 - 100 %]
Figure 6.9 Preset Reference
Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
Table 6.4 Bits per Preset Reference
3-11 Jog Speed [Hz]
Range:
Function:
Size
related
*
[ 0 - par.
4-14 Hz]
The jog speed is a fixed output speed
at which the adjustable frequency
drive is running when the jog
function is activated.
See also
3-80 Jog Ramp Time
.
3-15 Reference Resource 1
Option:
Function:
Select the reference input to be used
for the first reference signal.
parameter 3-15 Reference Resource 1
,
parameter 3-16 Reference Resource 2
and
parameter 3-17 Reference Resource 3
define up to three different reference
signals. The sum of these reference
signals defines the actual reference.
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Frequency input
29
[8]
Frequency input
33
[11] Local bus
reference
[20] Digital pot.meter
[21] Analog input
X30-11
(General Purpose I/O Option Module)
[22] Analog input
X30-12
(General Purpose I/O Option Module)
[29] Analog Input
X48/2
3-16 Reference Resource 2
Option:
Function:
Select the reference input to be used
for the second reference signal.
parameter 3-15 Reference Resource 1
parameter 3-16 Reference Resource 2
and
parameter 3-17 Reference Resource
define up to three different reference
signals. The sum of these reference
signals defines the actual reference.
[0]
No function
[1]
Analog Input 53
[2]
Analog Input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11] Local bus reference
[20] Digital pot.meter
[21] Analog input
X30-11
[22] Analog input
X30-12
[29] Analog Input X48/2