16-57 Feedback [RPM]
Range:
Function:
0 RPM
*
[-30000 -
30000 RPM]
Readout parameter where the actual motor
RPM from the feedback source can be read
in both closed loop and open loop. The
feedback source is selected in
parameter 7-00 Speed PID Feedback Source
.
4.15.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
*
[0 -
65535 ]
View the actual state of the digital inputs 18,
19, 27 and 29.
Bit 0
Unused
Bit 1
Unused
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6-15 Unused
Table 4.9 Bits Definition
16-61 Terminal 53 Setting
Option:
Function:
View the setting of input terminal 53.
[0] Current mode
[1] Voltage mode
16-62 Analog Input 53
Range:
Function:
1
*
[0 - 20 ]
View the actual value at input 53.
16-63 Terminal 54 Setting
Option:
Function:
View the setting of input terminal 54.
[0] Current mode
[1] Voltage mode
16-64 Analog Input AI54
Range:
Function:
1
*
[0 - 20 ]
View the actual value at input 54.
16-65 Analog Output 42 [mA]
Range:
Function:
0 mA
*
[0 - 20
mA]
View the actual value at output 42. The
value shown reflects the selections in
parameter 6-90 Terminal 42 Mode
and
parameter 6-91 Terminal 42 Analog Output
16-66 Digital Output
Range:
Function:
0
*
[0 - 15 ]
View the binary value of all digital outputs.
16-67 Pulse Input #29 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual frequency rate on terminal 29.
16-68 Pulse Input 33 [Hz]
Range:
Function:
0
*
[0 - 130000 ] View the actual value of the frequency
applied at terminal 33 as an impulse input.
16-69 Pulse Output 27 [Hz]
Range:
Function:
0
*
[0 - 40000 ] View the actual value of impulses applied to
terminal 27 in digital output mode.
16-70 Pulse Output 29 [Hz]
Range:
Function:
0
*
[0 - 40000 ] View the actual value of pulses to terminal 29
in digital output mode.
16-71 Relay Output
Range:
Function:
0
*
[0 - 65535 ]
View the settings of all relays.
16-72 Counter A
Range:
Function:
0
*
[-32768 -
32767 ]
View the present value of counter A. Counters are
useful as comparator operands, see
parameter 13-10 Comparator Operand
.
The value can be reset or changed either via
digital inputs (parameter group
5-1* Digital
Inputs
), or by using an SLC action
(
parameter 13-52 SL Controller Action
16-73 Counter B
Range:
Function:
0
*
[-32768 -
32767 ]
View the present value of counter B. Counters are
useful as comparator operands
(
parameter 13-10 Comparator Operand
The value can be reset or changed either via
digital inputs (parameter group
5-1* Digital
Inputs
) or by using an SLC action
(
parameter 13-52 SL Controller Action
).
16-79 Analog Output AO45
Range:
Function:
0 mA
*
[0 - 20
mA]
View the actual value at output 45 in mA.
The value shown reflects the selection in
parameter 6-70 Terminal 45 Mode
and
parameter 6-71 Terminal 45 Analog Output
Parameter Descriptions
VLT
®
AutomationDrive FC 360
104
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
4
4