1.3 Electrical Wiring - Control Cables
1.3.1 Overview
130BC438.16
3 phase
power
input
Switch Mode
Power Supply
Motor
Analog Output
Interface
(PNP) = Source
(NPN) = Sink
ON=Terminated
OFF=Open
Brake
resistor
91 (L1)
92 (L2)
93 (L3)
PE
50 (+10 V OUT)
53 (A IN)
54 (A IN)
55 (COM A IN)
0/4-20 mA
12 (+24 V OUT)
31 (D IN)
18 (D IN)
20 (COM D IN)
10 V DC
15 mA
100 mA
+
-
+
-
(U) 96
(V) 97
(W) 98
(PE) 99
(A OUT) 45
(A OUT) 42
(P RS485) 68
(N RS485) 69
(COM RS485) 61
0V
5V
S801
0/4-20 mA
RS485
RS485
03
+10 V DC
0/4-20 mA
0-10 V DC
24 V DC
02
01
05
04
240 V AC, 3 A
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
19 (D IN)
24 V (NPN)
0 V (PNP)
27 (D IN/OUT)
24 V
0 V
0 V (PNP)
24 V (NPN)
0 V
24 V
29 (D IN/OUT)
24 V (NPN)
0 V (PNP)
0 V (PNP)
24 V (NPN)
33 (D IN)
32 (D IN)
95
P 5-00
2
1
ON
(+UDC) 89
(BR) 81 5)
24 V (NPN)
0 V (PNP)
0-10 V DC
(-UDC) 88
RFI
3)
0 V
240 V AC, 3 A
Relay 1
1)
Relay 2 2)
4)
06
Illustration 1.3 Basic Wiring Schematic Drawing
A = Analog, D = Digital
1) Built-in brake chopper available from 0.37–22 kW.
2) Relay 2 is 2-pole for J1–J3 and 3-pole for J4–J7. Relay 2 of J4–J7 with terminal 4, 5, 6, same NO/NC logic as Relay 1. Relays
are pluggable in J1–J5, and fixed in J6–J7.
3) Dual DC choke in 30–75 kW (J6–J7).
4) Switch S801 (bus terminal) can be used to enable termination on the RS485 port (terminals 68 and 69).
5) No BR for 30–75 kW (J6–J7).