5-30 Terminal 27 Digital Output
Option:
Function:
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[91]
Encoder emulate output A
[160]
No alarm
[161]
Running reverse
[165]
Local ref active
[166]
Remote ref active
[167]
Start command activ
[168]
Drive in hand mode
[169]
Drive in auto mode
[170]
Homing Completed
[171]
Target Position Reached
[172]
Position Control Fault
[173]
Position Mech Brake
[174]
TLD indicator
[175]
Running on tension
[176]
Ready to run
[177]
End of roll
[193]
Sleep Mode
[194]
Broken Belt Function
5-31 Terminal 29 Digital Output
Option:
Function:
[0]
*
No operation Functions are described in parameter group
5-3* Digital Outputs
.
5-34 On Delay, Digital Output
Range:
Function:
0.01 s
*
[0 - 600 s]
5-35 Off Delay, Digital Output
Range:
Function:
0.01 s
*
[0 - 600 s]
4.6.4 5-4* Relays
Parameters for configuring the timing and the output
functions for the relays.
The parameter is an array parameter representing 2 relays:
Array [2] (Relay 1 [0], Relay 2 [1]).
5-40 Function Relay
Option:
Function:
[0]
No operation
Default setting for all digital and relay
outputs.
[1]
Control Ready
The control card is ready.
5-40 Function Relay
Option:
Function:
[2]
Drive ready
The frequency converter is ready to
operate. Mains and control supplies are
OK.
[3]
Drive rdy/rem ctrl The frequency converter is ready for
operation, and is in
Auto On
mode.
[4]
Stand-by / no
warning
Ready for operation. No start or stop
commands have been applied. No
warnings are active.
[5]
Running
The motor is running and a shaft
torque is present.
[6]
Running / no
warning
The output speed is higher than the
speed set in
parameter 1-82 Min Speed
for Function at Stop [Hz]
. The motor is
running and no warnings are present.
[7]
Run in range/no
warn
The motor is running within the
programmed current ranges set in
parameter 4-50 Warning Current Low
.
[8]
Run on ref/no
warn
The motor runs at reference speed. No
warnings.
[9]
Alarm
An alarm activates the output. No
warnings.
[10]
Alarm or warning An alarm or warning activates the
output.
[11]
At torque limit
The torque limit set in
parameter 4-16 Torque Limit Motor Mode
or
has been exceeded.
[12]
Out of current
range
The motor current is outside the range
set in
.
[13]
Below current,
low
The motor current is lower than set in
parameter 4-50 Warning Current Low
.
[14]
Above current,
high
The motor current is higher than set in
parameter 4-51 Warning Current High
.
[15]
Out of frequency
range
The output speed/frequency exceeds
the limit that is set in
parameter 4-40 Warning Freq. Low
and
parameter 4-41 Warning Freq. High
.
[16]
Below frequency,
low
The output frequency is lower than the
setting in
.
[17]
Above frequency,
high
The frequency is higher than the
setting in
[18]
Out of feedb.
range
The feedback is outside the range set
in
parameter 4-56 Warning Feedback
and
Parameter Descriptions
Programming Guide
MG06C602
Danfoss A/S © 7/2015 All rights reserved.
55
4
4