37-28 TLD High Limit
Set the high limit for the tension limit detection.
Range:
Function:
0 %
*
[0 - 100 %]
37-29 TLD Timer
Sets the time within which the tension must exceed the high or
low tension limit.
Range:
Function:
0.001 s
*
[0.001 - 5 s]
37-30 TLDOnDelay
Enable this parameter to allow time for the winder to stabilise
the web tension. As soon as the tension moves within the low
and high tension limits, the TLD function begins operating
normally. This function can be useful during a quick machine
start with a slack web. This function is only active while running.
Option:
Function:
[0]
Disabled
[1]
*
Enabled
37-31 Diameter Limit Detector
When the calculated roll diameter reaches the set diameter, the
corresponding digital output is turned on to indicate the end of
the roll. This indicates a full roll when winding and an empty roll
when unwinding.
Range:
Function:
100 %
*
[0 - 100 %]
37-32 Initial Diameter Measurement
It is possible to connect a roll diameter sensor to one of the
frequency converter analog inputs. This signal can be used to
make the controller use a measured initial diameter, rather than a
diameter size set by parameters.
Option:
Function:
[0]
*
Set diameter when
diameter reset
[1]
Set diameter based on
analog signal
37-33 Diameter Measurement Input
Use this parameter to set the analog input used for diameter
measurement.
Option:
Function:
[0]
*
No Function
[1]
Input53(0~10 VDC or 0~20
mA )
[2]
Input54(0~10 VDC or 0~20
mA )
37-34 Reading at Core
Use this parameter to set the analog input signal reading at the
smallest core used.
Range:
Function:
0
*
[0 - 10 ]
37-35 Reading at Full Roll
Use this parameter to set the analog input signal reading at the
full roll size used.
Range:
Function:
0 V
*
[0 - 20 V]
37-36 Tension Set Point Input
Use this parameter to set the source of the tension setpoint.
Option:
Function:
[0]
*
Par.3721
[1]
Input53(0~10 VDC or 0~20 mA )
[2]
Input54(0~10 VDC or 0~20 mA )
37-37 Taper Set Point Input
Use this parameter to set the source of the taper setpoint.
Option:
Function:
[0]
*
Par.3722
[1]
Input53(0~10 VDC or 0~20 mA )
[2]
Input54(0~10 VDC or 0~20 mA )
37-38 Tension Feedback Input
Use this parameter to set analog input used for tension feedback.
Option:
Function:
[0]
*
No Function
[1]
Input53(0~10 VDC or 0~20 mA )
[2]
Input54(0~10 VDC or 0~20 mA )
37-39 Tension Feedback Type
Selects the device type used for tension feedback.
Option:
Function:
[0]
*
Load cell
[1]
Dancer
37-40 Center Winder Cmd Src
Use this parameter to configure the command source for
controlling.
Option:
Function:
[0]
Digital and parameter
[1]
*
Parameter 3754~3759 control the
functions
[2]
Digital input control
37-41 Diameter Change Rate
Sets the amount of changes allowed for the diameter in each
program scan.
Range:
Function:
0.001 %
*
[0.001 - 0.05 %]