8-43 PCD Read Configuration
Enter up to 16 different preset mapping (0-15) in this parameter,
using array programming. If this parameter is active, addresses
from 2910 to 2925 represent values of the 16 parameters. If this
parameter is not active, addresses 2910 and 2911 are used as
status word register and main actual value. Addresses from 2912
to 2925 are reserved.
Option:
Function:
[18]
[1630] DC Link Voltage
[19]
[1634] Heatsink Temp.
[20]
[1635] Inverter Thermal
[21]
[1638] SL Controller State
[22]
[1650] External Reference
[23]
[1652] Feedback [Unit]
[24]
[1660] Digital Input 18,19,27,33
[25]
[1661] Terminal 53 Switch
Setting
[26]
[1662] Analog Input 53(V)
[27]
[1663] Terminal 54 Switch
Setting
[28]
[1664] Analog Input 54
[29]
[1665] Analog Output 42 [mA]
[30]
[1671] Relay Output [bin]
[31]
[1672] Counter A
[32]
[1673] Counter B
[33]
[1690] Alarm Word
[34]
[1692] Warning Word
[35]
[1694] Ext. Status Word
[38]
[1622] Torque [%]
4.9.5 8-5* Digital/Bus
Parameters for configuring the control word merging.
NOTICE
These parameters are active only when
parameter 8-01 Control Site
is set to
[0] Digital and control
word
.
8-50 Coasting Select
Option:
Function:
Select control of the coasting function via the
terminals (digital input) and/or via the bus.
[0]
Digital
input
Activates start command via a digital input.
[1]
Bus
Activates start command via the serial
communication port or fieldbus option.
[2]
Logic AND Activates start command via the fieldbus/serial
communication port, and 1 extra digital input.
[3]
*
Logic OR
Activates start command via the fieldbus/serial
communication port, or via 1 of the digital
inputs.
8-51 Quick Stop Select
Select control of the quick stop function via the terminals (digital
input) and/or via the bus.
Option:
Function:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
*
Logic OR
8-52 DC Brake Select
Option:
Function:
Select control of the DC brake via the terminals
(digital input) and/or via the fieldbus.
NOTICE
When
parameter 1-10 Motor Construction
is set to
[1] PM non-salient SPM
, only
selection
[0] Digital input
is available.
[0]
Digital
input
Activates start command via a digital input.
[1]
Bus
Activates start command via the serial communi-
cation port or fieldbus option.
[2]
Logic
AND
Activates start command via the fieldbus/serial
communication port, and additionally via 1 of
the digital inputs.
[3]
*
Logic OR Activates start command via the fieldbus/serial
communication port, or via 1 of the digital
inputs.
8-53 Start Select
Option:
Function:
Select control of the frequency converter start
function via the terminals (digital input) and/or
via the fieldbus.
[0]
Digital
input
Activates a start command via a digital input.
[1]
Bus
Activates a start command via the serial
communication port or fieldbus option.
[2]
Logic
AND
Activates a start command via the fieldbus/serial
communication port, and additionally via 1 of
the digital inputs.
[3]
*
Logic OR
Activates a start command via the fieldbus/serial
communication port, or via 1 of the digital
inputs.
8-54 Reversing Select
Option:
Function:
[0] Digital
input
Select control of the frequency converter reverse
function via the terminals (digital input) and/or
via the fieldbus.
[1] Bus
Activates the reverse command via the serial
communication port or fieldbus option.
Parameter Descriptions