converter has received a stop signal and
is at the torque limit, the signal is logic 0.
[28]
Brake, no brake
warning
The brake is active and there are no
warnings.
[29]
Brake ready, no
fault
The brake is ready for operation and
there are no faults.
[30]
Brake fault
(IGBT)
The output is logic 1 when the brake
IGBT is short-circuited. Use this function
to protect the frequency converter if
there is a fault on the brake modules. Use
the output/relay to cut out the mains
voltage from the frequency converter.
[31]
Relay 123
The relay is activated when
[0] Control
Word
is selected in parameter group
8-**
Communications and Options
.
[32]
Mechanical
brake control
Enables control of an external mechanical
brake. See parameter group
2-2*
Mechanical Brake
for more details.
[36]
Control word
bit 11
[37]
Control word
bit 12
[40]
Out of ref
range
This option is active when the actual
speed is outside the settings in
parameter 4-52 Warning Speed Low
to
parameter 4-55 Warning Reference High
.
[41]
Below
reference low
This option is active when the actual
speed is below the speed reference
setting.
[42]
Above
reference high
This option is active when the actual
speed is above the speed reference
setting.
[45]
Bus Ctrl
Controls output via fieldbus. The state of
the output is set in
parameter 5-90 Digital
& Relay Bus Control
. The output state is
retained in the event of fieldbus timeout.
[46]
Bus Ctrl On at
timeout
Controls output via fieldbus. The state of
the output is set in
parameter 5-90 Digital
& Relay Bus Control
. When bus timeout
occurs, the output state is set high (On).
[55]
Pulse output
[56]
Heat sink
cleaning
warning, high
[60]
Comparator 0
See parameter group
13-1* Comparators
.
If comparator 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[61]
Comparator 1
See parameter group
13-1* Comparators
.
If comparator 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[62]
Comparator 2
See parameter group
13-1* Comparators
.
If comparator 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[63]
Comparator 3
See parameter group
13-1* Comparators
.
If comparator 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[64]
Comparator 4
See parameter group
13-1* Comparators
.
If comparator 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[65]
Comparator 5
See parameter group
13-1* Comparators
.
If comparator 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[70]
Logic Rule 0
See parameter group
13-4* Logic Rules
. If
logic rule 0 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[71]
Logic Rule 1
See parameter group
13-4* Logic Rules
. If
logic rule 1 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[72]
Logic Rule 2
See parameter group
13-4* Logic Rules
. If
logic rule 2 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[73]
Logic Rule 3
See parameter group
13-4* Logic Rules
. If
logic rule 3 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[74]
Logic Rule 4
See parameter group
13-4* Logic Rules
. If
logic rule 4 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[75]
Logic Rule 5
See parameter group
13-4* Logic Rules
. If
logic rule 5 is evaluated as TRUE, the
output goes high. Otherwise, it is low.
[80]
SL Digital
Output A
See
parameter 13-52 SL Controller Action
.
The output goes high whenever the
smart logic action
[38] Set dig. out. A high
is executed. The output goes low
whenever the smart logic action
[32] Set
dig. out. A low
is executed.
[81]
SL Digital
Output B
See
parameter 13-52 SL Controller Action
.
The input goes high whenever the smart
logic action
[39] Set dig. out. B high
is
executed. The input goes low whenever
the smart logic action
[33] Set dig. out. B
low
is executed.
[82]
SL Digital
Output C
See
parameter 13-52 SL Controller Action
.
The input goes high whenever the smart
logic action
[40] Set dig. out. C high
is
executed. The input goes low whenever
the smart logic action
[34] Set dig. out. C
low
is executed.
[83]
SL Digital
Output D
See
parameter 13-52 SL Controller Action
.
The input goes high whenever the smart
logic action
[41] Set dig. out. D high
is
executed. The input goes low whenever
the smart logic action
[35] Set dig. out. D
low
is executed.
[160] No alarm
The output is high when no alarm is
present.
[161] Running
reverse
The output is high when the frequency
converter is running counterclockwise
(the logical product of the status bits
Running
AND
Reverse
).
[165] Local reference
active
Parameter Descriptions
Programming Guide
MG06C602