5-65 Pulse Output Max Freq 29
Range:
Function:
5000 Hz
*
[4 - 32000
Hz]
Set the maximum frequency for terminal
29 corresponding to the output variable
set in
parameter 5-63 Terminal 29 Pulse
4.6.7 5-7* 24 V Encoder Input
Connect the 24 V encoder to terminal 12 (24 V DC supply),
terminal 32 (channel A), terminal 33 (channel B), and
terminal 20 (GND). The digital inputs 32/33 are active for
encoder inputs when
[1] 24 V encoder
is selected in
parameter 7-00 Speed PID Feedback Source
. The encoder is a
dual channel (A and B) 24 V type. Maximum input
frequency: 32 kHz.
Encoder connection to the frequency converter
24 V incremental encoder. Maximum cable length 5 m.
130BD366.12
+24
V DC
A
B
GND
12
18
32
27
19
29
33
20
Illustration 4.16 24 V or 10–30 V Encoder Connection
B
A
B
A
130BA646.10
CW
CCW
Illustration 4.17 Encoder Rotation Direction
5-70 Term 32/33 Pulses Per Revolution
Range:
Function:
1024
*
[1 - 4096 ] Set the encoder pulses per revolution on the
motor shaft. Read the correct value from the
encoder.
5-71 Term 32/33 Encoder Direction
Option:
Function:
NOTICE
This parameter cannot be changed
while the motor is running.
Change the detected encoder rotation
direction without changing the wiring to the
encoder.
[0]
*
Clockwise
Sets channel A 90
°
(electrical degrees)
behind channel B upon clockwise rotation of
the encoder shaft.
[1]
Counter
clockwise
Sets channel A 90
°
(electrical degrees) ahead
of channel B upon clockwise rotation of the
encoder shaft.
Parameter Descriptions
VLT
®
AutomationDrive FC 360
60
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
4