5.2.24 37-** Application Settings
Par. No. #
Parameter description
Default value
2-set-up
Change during
operation
Conversion
index
Type
37-0* Application Mode
37-00
Application Mode
[0] Drive mode
1 set-up
FALSE
–
Uint8
37-1* Position Control
37-01
Pos. Feedback Source
[0] 24 V Encoder
1 set-up
FALSE
–
Uint8
37-02
Pos. Target
0 N/A
1 set-up
FALSE
0
Int32
37-03
Pos. Type
[0] Absolute
1 set-up
FALSE
–
Uint8
37-04
Pos. Velocity
100 RPM
1 set-up
FALSE
67
Uint16
37-05
Pos. Ramp Up Time
5000 ms
1 set-up
FALSE
-3
Uint32
37-06
Pos. Ramp Down Time
5000 ms
1 set-up
FALSE
-3
Uint32
37-07
Pos. Auto Brake Ctrl
[1] Enable
1 set-up
TRUE
–
Uint8
37-08
Pos. Hold Delay
0 ms
1 set-up
TRUE
-3
Uint32
37-09
Pos. Coast Delay
200 ms
1 set-up
TRUE
-3
Uint16
37-10
Pos. Brake Delay
200 ms
1 set-up
TRUE
-3
Uint16
37-11
Pos. Brake Wear Limit
0 N/A
1 set-up
TRUE
0
Uint32
37-12
Pos. PID Anti Windup
[1] Enable
1 set-up
TRUE
–
Uint8
37-13
Pos. PID Output Clamp
1000 N/A
1 set-up
TRUE
0
Uint16
37-14
Pos. Ctrl. Source
[0] DI
1 set-up
TRUE
–
Uint8
37-15
Pos. Direction Block
[0] No Blocking
1 set-up
TRUE
–
Uint8
37-16
Pos. Power Recovery
[1] Enable
1 set-up
TRUE
–
Uint8
37-17
Pos. Ctrl Fault Behaviour
[0] Ramp Down&Brake
1 set-up
FALSE
–
Uint8
37-18
Pos. Ctrl Fault Reason
[0] No Fault
1 set-up
TRUE
–
Uint8
37-19
Pos. New Index
0 N/A
1 set-up
TRUE
–
Uint8
37-2* Center Winder
1 set-up
37-20
Winder Mode Selection
[0] Wind
1 set-up
FALSE
–
Uint8
37-21
Tension Set Point
0%
1 set-up
TRUE
-1
Uint16
37-22
Taper Set Point
0%
1 set-up
TRUE
-1
Int16
37-23
Partial Roll Diameter Value
5%
1 set-up
FALSE
-3
Uint32
37-24
Core1 Diameter
5%
1 set-up
FALSE
-3
Uint32
37-25
Core2 Diameter
5%
1 set-up
FALSE
-3
Uint32
37-26
Winder Jog Speed
0%
1 set-up
TRUE
0
Uint8
37-27
TLD Low Limit
0%
1 set-up
TRUE
-1
Uint16
37-28
TLD High Limit
0%
1 set-up
TRUE
-1
Uint16
37-29
TLD Timer
0.001 s
1 set-up
TRUE
-3
Uint16
37-30
TLDOnDelay
[1] Enabled
1 set-up
TRUE
–
Uint8
37-31
Diameter Limit Detector
100%
1 set-up
TRUE
-3
Uint32
37-32
Initial Diameter Measurement
[0] Set diameter when
diameter reset
1 set-up
FALSE
–
Uint8
37-33
Diameter Measurement Input
[0] No Function
1 set-up
FALSE
–
Uint8
37-34
Reading at Core
0 N/A
1 set-up
TRUE
-2
Int16
37-35
Reading at Full Roll
0 V
1 set-up
TRUE
-2
Int16
37-36
Tension Set Point Input
[0] Par.3721
1 set-up
FALSE
–
Uint8
37-37
Taper Set Point Input
[0] Par.3722
1 set-up
FALSE
–
Uint8
37-38
Tension Feedback Input
[0] No Function
1 set-up
FALSE
–
Uint8
37-39
Tension Feedback Type
[0] Load cell
1 set-up
FALSE
–
Uint8
37-40
Center Winder Cmd Src
[1] Parameter
3754~3759 control the
functions
1 set-up
TRUE
–
Uint8
37-41
Diameter Change Rate
0.001%
1 set-up
TRUE
-3
Uint8
37-42
Tapered Tension Change Rate
0.1%
1 set-up
TRUE
-1
Uint8
Parameter Lists
VLT
®
AutomationDrive FC 360
142
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
5