4.7.4 6-7* Analog/Digital Output 45
Parameters for configuring the scaling and limits for
analog/digital output terminal 45. Analog outputs are
current outputs: 0/4-20 mA. Resolution on analog output is
12 bit. Analog output terminals can also be set up as
digital output.
6-70 Terminal 45 Mode
Option:
Function:
Set terminal 45 to act as analog output or
as digital output.
[0]
*
0-20 mA
[1]
4-20 mA
[2]
Digital Output
6-71 Terminal 45 Analog Output
Option:
Function:
[0]
*
No operation
[100]
Output frequency
0–100 Hz
[101]
Reference
Min
Ref
–Max
Ref
[102]
Process Feedback
Min
FB
–Max
FB
[103]
Motor Current
0–I
max
[104]
Torque rel to limit
[105]
Torq relate to rated
[106]
Power
0–P
nom
[107]
Speed
[111]
Speed Feedback
[113]
Ext. Closed Loop 1
[139]
Bus Control
0–100%
[143]
Ext. CL 1
[162]
Tapered tension set point
[254]
DC Link Voltage
6-72 Terminal 45 Digital Output
Option:
Function:
Select the function of terminal 45
as a digital current output. See
also
parameter 6-70 Terminal 45
Mode
. See
for descriptions of the
option.
[0]
*
No operation
[1]
Control Ready
[2]
Drive ready
[3]
Drive rdy/rem ctrl
[4]
Stand-by / no warning
[5]
Running
[6]
Running / no warning
[7]
Run in range/no warn
[8]
Run on ref/no warn
[9]
Alarm
[10]
Alarm or warning
6-72 Terminal 45 Digital Output
Option:
Function:
[11]
At torque limit
[12]
Out of current range
[13]
Below current, low
[14]
Above current, high
[15]
Out of frequency
range
[16]
Below frequency, low
[17]
Above frequency, high
[18]
Out of feedb. range
[19]
Below feedback, low
[20]
Above feedback, high
[21]
Thermal warning
[22]
Ready, no thermal
warning
[23]
Remote,ready,no TW
[24]
Ready, no over-/ under
voltage
[25]
Reverse
[26]
Bus OK
[27]
Torque limit & stop
[28]
Brake, no brake
warning
[29]
Brake ready, no fault
[30]
Brake fault (IGBT)
[31]
Relay 123
[32]
Mech brake ctrl
[36]
Control word bit 11
[37]
Control word bit 12
[40]
Out of ref range
[41]
Below reference, low
[42]
Above ref, high
[45]
Bus ctrl.
[46]
Bus control, timeout:
On
[47]
Bus control, timeout:
Off
[56]
Heat sink cleaning
warning, high
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
Parameter Descriptions
VLT
®
AutomationDrive FC 360
64
Danfoss A/S © 7/2015 All rights reserved.
MG06C602
4
4