SiUS092230EA
Forced Cooling Operation
Part 7 Trial Operation and Field Settings
207
FDMQ, FFQ Series
R7000383
With Wired Remote Controller (BRC1E73)
With Wireless Remote Controller (BRC082A43, BRC082A41W, BRC082A42W(S))
1. Set to COOL operation using the remote
controller.
2. Press and hold
Cancel
button for 4 seconds
or longer. Service settings menu is
displayed.
3. Select
in the service
settings menu, and press
Menu/OK
button.
Basic screen returns and “Test Operation”
is displayed at the bottom.
4. Press
On/Off
button within 10 seconds, and
the forced cooling operation starts.
Forced cooling operation will stop
automatically after about 15 minutes.
To stop the operation, press
On/Off
button.
1. Press
button and select the COOL
operation.
2. Press
button twice.
“
TEST
”
is
displayed.
3. Press
button within 10 seconds, and
the forced cooling operation starts.
Forced cooling operation will stop
automatically after about 15 minutes.
To stop the operation, press
button.
Test Operation
Basic screen
1.
2.
3.
4.
Service Settings
menu screen
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
Press Menu/OK button.
Press On/Off button
(within 10 seconds).
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...