Field Settings for FDMQ, FFQ Series
SiUS092230EA
224
Part 7 Trial Operation and Field Settings
Wireless Remote
Controller
Address
Factory set is 1. Change the wireless remote controller address setting by the following steps, if
necessary.
1. Hold down
button and
/TEST button at the same time for at least 4 seconds to enter the
field setting mode. (SETTING is indicated on the display).
Press FAN button and select display setting (
A
or
b
). Each time the button is pressed, the
display switches between
A
and
b
.
2. Press button and button to set the address.
Address can be set from 1 ~ 6, but set it to 1 ~ 3 and to same address as the transmitter board.
The transmitter board does not work with address 4 ~ 6.
3. Press
RESERVE
button to confirm the setting.
4. Hold down
/TEST button to quit the field setting mode and return to the normal display.
Field setting mode
Address
Multiple setting
(R14401)