Troubleshooting for FDMQ, FFQ Series
Part 6 Service Diagnosis
141
6.3 Indoor Fan Motor or Related Abnormality
6.3.1 Indoor Fan Motor (DC Motor) or Related Abnormality
Applicable
Models
FDMQ09/12/15/18/24WVJU9
Error Code
A6
Method of Error
Detection
Detection from the current flow on the fan PCB
Detection from the rotation speed of the fan motor in operation
Error Decision
Conditions
The rotation speed is less than a certain level for 6 seconds.
Supposed
Causes
Clogged foreign matter
Disconnection of fan motor connectors
Disconnection of the connector between the indoor unit PCB and the fan PCB
Defective fan PCB
Defective fan motor
No fuse continuity
Trouble Shooting
R6000547
Connect the connector
correctly.
Turn OFF the power supply
and wait for 10 minutes.
NO
YES
NO
Connect the connector
correctly.
NO
YES
YES
Replace the fuse.
There is a
continuity in the fuse
(
∗
2) on the fan PCB or fan
motor harness.
NO
The fan motor
connector (
∗
1) is
connected to the fan
PCB.
Remove the foreign matter.
YES
There is a foreign
matter around the fan.
The connector
between the indoor unit
control PCB and the fan
PCB is connected.
A
Go to the next page
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...