Field Settings for Outdoor Unit
SiUS092230EA
226
Part 7 Trial Operation and Field Settings
Reference
Caution
Caution
6. Field Settings for Outdoor Unit
6.1 Facility Setting (cooling at low outdoor temperature)
Outline
This function is limited only for facilities (the target of air conditioning is equipment such as
computers). Never use it in a residence or office (the space where there is a human).
Details
Cutting jumper J6 on the outdoor unit PCB will extend the operation range to 14°F (–10°C).
Installing an air direction adjustment grille (sold separately) will further extend the operation
range to –4°F (–20°C). In these cases, the unit will stop operating if the outdoor temperature
falls below –4°F (–20°C), restarting once the temperature rises above this level.
(1) Remove the top plate of the outdoor unit. (09/12 class: 4 screws, 15/18/24 class: 6 screws)
(2) Remove the front plate. (09/12 class: 5 screws, 15/18/24 class: 8 screws)
(3) Cut the jumper J6 of the PCB inside.
09/12 class
R7000390
15/18/24 class
R7000391
For the location of the jumper, refer to pages 34, 36.
If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind,
provide a windbreak wall.
Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off
when using facility settings.
Do not place humidifiers or other items which might raise the humidity in rooms where facility
settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.
Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.
Replace the remote controller if you cut a jumper unintentionally
.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
Cut the jumper (J6).
J6
J5
J9
J12
J8
J11
Cut jumper (J6).
J9
J4
J6
J5
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...