Functions for FDMQ/FFQ Series
SiUS092230EA
74
Part 4 Functions and Control
2. Auto-setback by sensor (with presence sensor)
After pre-determined time has elapsed without detection of human presence, the unit automatically
shifts the target temperature gradually for energy saving.
The target temperature displayed on the remote controller remains same as the initial set value
during the above change of target temperature.
The target temperature shifts within the range of the highest programmable temperature while in
cooling operation and the lowest programmable temperature while in heating operation.
Upon human detection, the target temperature returns to the original setting.
Auto-setback by sensor is enabled only when decoration panel BYFQ60C2W1W(S), sensor kit
BRYQ60A2W(S) and wired remote controller BRC1E73 are connected to the main unit and
auto-setback by sensor is set to “enabled” on the wired remote controller.
Factory setting is “disabled”.
Setting on the remote controller
R4003390
2
3
4
5
1
Press buttons to select
Auto-setback by Sensor
.
Press
Menu/OK
button to display
Auto-setback by Sensor menu.
Press buttons to select
Enable/
Disable
.
Press
Menu/OK
button.
Press buttons to select
Enable
.
Press
Menu/OK
button after selecting
the item. Then the confirmation screen
is displayed.
Press buttons to select
Yes
.
Press
Menu/OK
button to confirm the
settings and to return to the Service
Settings menu.
Press
Cancel
button for 4 seconds on
the basic screen to display Service
Settings menu.
Press buttons to select
Energy
Saving Options
.
Press
Menu/OK
button to display
Energy Saving Options menu.
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Setting
Energy Saving Options
Setpoint Range Limitation
Auto-setback by Sensor
Auto-off by Sensor
Setting
Enable/Disable
Settings
Auto-setback by Sensor
Setting
Enable/Disable
Auto-setback by Sensor
Enable
Setting
Save the settings?
Auto-setback by Sensor
Yes
No
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...