SiUS092230EA
Field Settings for Outdoor Unit
Part 7 Trial Operation and Field Settings
227
Reference
Note(s)
6.2 Warmer Airflow Setting
Outline
The temperature of discharge airflow in heating operation can be adjusted warmer.
The room temperature will be high when getting close to the set temperature.
The discharge airflow does not become warmer in other than heating operation.
Procedure
Warmer airflow can be enabled from outdoor unit.
Cut the jumper (J5) of the PCB inside.
09/12 Class
R7000387
15/18/24 Class
R7000388
For the location of the jumper, refer to page 34, 36.
Warmer airflow can be enabled from either indoor or outdoor unit.
Warmer airflow becomes available when either one of the RC or outdoor unit setting is enabled.
For example, if the outdoor unit has the switch for warmer airflow, it can be set even when it is
disabled on the indoor unit.
Also, for the wireless remote controller with field setting function, warmer airflow is enabled when
set on indoor unit with the remote controller field setting, even when it is disabled on outdoor unit.
Cut the jumper (J5).
J6
J5
J9
J12
J8
J11
Cut jumper (J5).
J9
J4
J6
J5
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...