SiUS092230EA
Functions for FDMQ/FFQ Series
Part 4 Functions and Control
73
3.9 Presence and Floor Sensors (Option)
Applicable
Models
FFQ09/12/15/18W2VJU9(8)
Outline
With the human presence signal and the floor temperature signal from the optional sensor kit, the
system provides the energy saving control, or the comfortable temperature control and airflow
direction control preventing the direct draft to the human.
To use sensor related functions, a wired remote controller (BRC1E73) and optional sensor kit
(BRYQ60A2W(S)) are necessary to be installed.
Details
1. Draft prevention (with presence sensor)
When the sensor detects human presence during auto-swing operation, the system sets the airflow
direction parallel to the floor (position 0) to reduce unpleasant draft.
The operation returns to the normal auto-swing as the sensor detects no human in the room.
Draft prevention is enabled only when decoration panel BYFQ60C2W1W(S), sensor kit
BRYQ60A2W(S) and wired remote controller BRC1E73 are connected to the main unit and
draft prevention is set to “enabled” on the wired remote controller.
Factory setting is “disabled”.
Draft prevention cannot be activated when individual flap control is set, even if draft prevention
is enabled on the wired remote controller.
Setting on the wired remote controller
R4003392
1
Setting
Main Menu
Configuration
Current Settings
Clock & Calendar
2/3
2
Draft Prevention
Configuration
Setting
3
Enable
Draft Prevention
Enable/Disable
Setting
4
No
Yes
Draft Prevention
Save the settings?
Setting
Press
Menu/OK
button to display the
main menu screen.
Press buttons to select
Yes
.
The confirmation screen will appear
when
Menu/OK
button is pressed.
Press
Menu/OK
button to confirm the
settings and to return to the basic
screen.
Language
Contrast Adjustment
Display
Press buttons to select
Configuration
and press
Menu/OK
button.
Press buttons to select
Draft Prevention
and press
Menu/OK
button.
Press buttons to select
Enable
.
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...