Functions for FTXR Series
SiUS092230EA
44
Part 4 Functions and Control
2.3 Program
Dry
Operation
Outline
Program dry operation removes humidity while preventing the room temperature from lowering.
Since the microcomputer controls both the temperature and airflow rate, the temperature
adjustment and
FAN
setting buttons are inoperable.
Details
The microcomputer automatically sets the temperature and airflow rate. The difference between
the room thermistor temperature at start-up and the target temperature is divided into two zones.
Then, the unit operates in an appropriate capacity for each zone to maintain the temperature and
humidity at a comfortable level.
Thermostat turns on also when the room temperature is in the zone B for 10 minutes.
Room thermistor
temperature at start-up
Target temperature
X
Thermostat OFF point
Y
Thermostat ON point
Z
24°C or more
(75.2°F or more)
Room thermistor
temperature at start-up
X – 2.5°C
(X – 4.5°F)
X – 0.5°C
(X – 0.9°F)
18 ~ 23.5°C
(64.4 ~ 74.3°F)
X – 2.0°C
(X – 3.6°F)
X – 0.5°C
(X – 0.9°F)
17.5°C or less
(63.5°F or less)
18°C
(64.4°F)
X – 2.0°C
(X – 3.6°F)
X – 0.5°C = 17.5°C
(X – 0.9°F = 63.5°F)
Zone A = Thermostat OFF
Target temperature X
Zone B
Room temperature
Room temperature
Zone C = Thermostat ON
Y = X – 2.5
°
C (4.5
°
F)
or
Y = X – 2.0
°
C (3.6
°
F)
Z = X – 0.5
°
C (0.9
°
F)
X – 1.0
°
C (1.8
°
F)
(R24029)
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...