Control Specification
SiUS092230EA
82
Part 4 Functions and Control
5.3.2 Four Way Valve Switching
Outline
The four way valve coil is energized/not energized depending on the operation mode.
(Heating: ON, Cooling/Dry/Defrost: OFF)
In order to eliminate the switching sound as the four way valve coil switches from ON to OFF when
the heating is stopped, the OFF delay switch of the four way valve is carried out.
Details
OFF delay switch of four way valve
The four way valve coil is energized for 160 seconds after the operation is stopped.
5.3.3 Four Way Valve Operation Compensation
Outline
At the beginning of operation as the four way valve is switched, the pressure difference to activate
the four way valve is acquired when the output frequency is higher than a certain fixed frequency,
for a certain fixed time.
Details
Starting Conditions
1. When the compressor starts and the four way valve switches from OFF to ON
2. When the four way valve switches from ON to OFF during operation
3. When the compressor starts after resetting
4. When the compressor starts after the fault of four way valve switching
The lower limit of frequency keeps
A
Hz for
B
seconds for any of the conditions above.
When the outdoor temperature is above
C
in heating, the frequency decreases depending on the
outdoor temperature.
5.3.4 3-Minute Standby
Turning on the compressor is prohibited for 3 minutes after turning off.
The function is not used when defrosting.
09/12 class
15/18/24 class
Cooling Heating Cooling Heating
A
(Hz)
40
54
48
B
(seconds)
60
70
C
(°C)
10
15
(°F)
50
59
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...