Control Specification
SiUS092230EA
94
Part 4 Functions and Control
5.12.8 Target Discharge Pipe Temperature Control
The target discharge pipe temperature is obtained from the indoor and outdoor heat exchanger
temperature, and the electronic expansion valve opening is adjusted so that the actual discharge
pipe temperature becomes close to the target discharge pipe temperature. (Indirect SH
(superheating) control using the discharge pipe temperature)
The electronic expansion valve opening and the target discharge pipe temperature are adjusted
every
A
seconds. The opening degree of the electronic expansion valve is adjusted by the
following.
Target discharge pipe temperature
Actual discharge pipe temperature
Previous discharge pipe temperature
The time depends on the opening of the electronic expansion valve.
5.13 Malfunctions
5.13.1 Sensor Malfunction Detection
Sensor malfunction can be detected in the following thermistor:
1. Outdoor heat exchanger thermistor
2. Discharge pipe thermistor
3. Radiation fin thermistor
4. Outdoor temperature thermistor
5.13.2 Detection of Overcurrent and Overload
Outline
An excessive output current is detected and the OL temperature is observed to protect the
compressor.
Details
If the OL (compressor head) temperature exceeds 130°C (266°F) (depending on the model),
the system shuts down the compressor.
If the inverter current exceeds 12.0 ~ 20.0 A (depending on the model), the system shuts down
the compressor.
The upper limit of the current decreases when the outdoor temperature exceeds a certain level.
All outdoor units
A
(seconds)
10 ~ 30
SC
(Subcooling)
SH
(Superheating)
The target discharge pipe
temperature is set as to become
the target SH.
The inclination does not change
depending on the operating condition.
(R23014)
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...