![background image](http://html1.mh-extra.com/html/daikin/rx-w-series/rx-w-series_service-manual_3662825206.webp)
Check
SiUS092230EA
200
Part 6 Service Diagnosis
8.11 Outdoor Fan System Check
Check No.19
DC motor
8.12 Main Circuit Short Check
Check No.20
Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is about
0 V before checking
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is
or less than 1 k
, short circuit occurs on the main circuit.
09/12 class
(R21195)
YES
NO
NO
YES
Outdoor fan system is functioning.
Check the outdoor fan system.
Reconnect the connector.
Is
the outdoor fan
running?
Fan motor lead
wire connector
disconnected?
Go to
Check No. 16
.
Positive terminal (+) of
digital multimeter
~ (2, 3)
+ (4)
~ (2, 3)
– (1)
Negative terminal (–) of
digital multimeter
+ (4)
~ (2, 3)
– (1)
~ (2, 3)
Resistance is OK.
several k
~ several M
Resistance is NG.
0
or
(R20698)
1
2
3
4
Multimeter
–~
~
+
–
+