SiUS092230EA
Functions for FDMQ/FFQ Series
Part 4 Functions and Control
75
3. Auto-off by sensor (with presence sensor)
After pre-determined time has elapsed without detection of human presence, the unit automatically
stops operation.
The auto-off time can be set between 1- 24 hours by the hour.
Once the unit stops operation by auto-off function, the system would not restart even if the human
is detected again.
Auto-off by sensor is enabled only when decoration panel BYFQ60C2W1W(S), sensor kit
BRYQ60A2W(S) and wired remote controller BRC1E73 are connected to the main unit and
auto-off by sensor is set to “enabled” on the wired remote controller.
Factory setting is “disabled”.
Setting on the remote controller
R4003391
2
3
4
1
Press buttons to select
Auto-off by Sensor
.
Press
Menu/OK
button to display
Auto-off by Sensor menu.
Press buttons to select
Enable
.
Press buttons to go into the auto-off
time setting.
Press buttons to set auto-off hour(s)
(1 ~ 24).
Press
Menu/OK
button. Then the
confirmation screen is displayed.
Press
Cancel
button for 4 seconds on
the basic screen to display Service
Settings menu.
Press buttons to select
Energy
Saving Options
.
Press
Menu/OK
button to display
Energy Saving Options menu.
Setting
1/3
Service Settings
Test Operation
Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Function
Min Setpoints Differential
Setting
Energy Saving Options
Setpoint Range Limitation
Auto-setback by Sensor
Auto-off by Sensor
5
Setting
Auto-off by Sensor
Enable/Disable:
Enable
Auto-off in: 24 hr(s)
Setting
Auto-off by Sensor
Enable/Disable: Enable
Auto-off in:
24
hr(s)
Setting
Save the settings?
Auto-off by Sensor
Yes
No
Press buttons to select
Yes
.
Press
Menu/OK
button to confirm the
settings and to return to the Service
Settings menu.
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...