Trial Operation
SiUS092230EA
210
Part 7 Trial Operation and Field Settings
With BRC1E73 Wired Remote Controller
1. Set to COOL or HEAT operation using the
remote controller.
2. Press and hold
Cancel
button for 4 seconds
or longer. Service settings menu is
displayed.
3. In the case of a model having airflow
direction function, select
in the service settings menu, and press
Menu/OK
button. Basic screen returns and
“Test Operation” is displayed at the bottom.
4. Press
On/Off
button within 10 seconds, and
the test operation starts.
Monitor the operation of the indoor unit for a
minimum of 10 minutes. During test
operation, the indoor unit will continue to
cool/heat regardless of the temperature
setpoint and room temperature.
In the case of above-mentioned
procedures 3 and 4 in reverse order, test
operation can start as well.
5. Press
Menu/OK
button in the basic screen.
Main menu is displayed.
6. Select
in the main
menu and press
Menu/OK
button. Check
that airflow direction is actuated according
to the setting. For operation of airflow
direction setting, see the operation manual.
7. After the operation of airflow direction is
confirmed, press
Menu/OK
button.
Basic screen returns.
8. Press and hold
Cancel
button for 4 seconds
or longer in the basic screen.
Service settings menu is displayed.
9. Select
in the service
settings menu, and press
Menu/OK
button.
Basic screen returns and normal operation
is conducted.
Test operation will stop automatically
after 15 ~ 30 minutes. To stop the
operation, press
On/Off
button.
10. If the decoration panel has not been
installed, turn off the power after the test
operation (FFQ series only).
Test Operation
Airflow Direction
Test Operation
Change the airflow
direction by using
(Up/Down)
button.
Basic screen
1.
2.
3.
4.
5.
Main menu screen
6.
7.
8.
9.
Basic screen
Service Settings
menu screen
Press and hold
Cancel
button for 4 seconds or
longer during backlight lit.
Press
Menu/OK
button.
Press
On/Off
button
(within 10 seconds).
Press
Menu/OK
button.
Press
Menu/OK
button.
Press
Menu/OK
button.
Press and hold
Cancel
button for 4 seconds or
longer during backlight lit.
Press
Menu/OK
button.
Cool
Set to
68
F
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...