SiUS092230EA
Service Diagnosis
Part 6 Service Diagnosis
117
3.1.2 Method 2
1. Press the center of
Temp
button and
Mode
button at the same time.
SC
is displayed on the LCD.
R6000375
2. Select
SC
(service check) with
Temp
or
Temp
button.
3. Press
Mode
button to enter the service check mode.
The left-side number blinks.
R6000373
4. Press
Temp
or
Temp
button and change the number until you hear the two consecutive
beeps or the long beep.
5. Diagnose by the sound.
Beep: The left-side number does not correspond with the error code.
Two consecutive beeps: The left-side number corresponds with the error code but the
right-side number does not.
(R24046)
(R24047)
(R24048)