SiUS092230EA
Control Specification
Part 4 Functions and Control
79
Note(s)
5. Control Specification
5.1 Mode
Hierarchy
Outline
The air conditioner control has normal operation mode, forced operation mode, and power
transistor test mode for installation and servicing.
Details
Unless specified otherwise, dry operation command is regarded as cooling operation.
5.2 Frequency
Control
Outline
The compressor frequency is determined according to the difference between the room thermistor
temperature and the target temperature.
Air conditioner control mode
Forced operation mode
Forced cooling operation (for pump down operation)
Power transistor test mode
Normal operation mode
Fan
Cooling (includes drying)
Heating
Heating
Defrosting
Stop (indoor unit: OFF)
Preheating control
Discharging from capacitor
Stop
(R22375)
Command frequency
Limit frequency
Skip control
Upper limit function
Compressor protection function
Lower limit function
Four way valve operation compensation, etc.
Target frequency
(R18023)
When the shift of the frequency is less than zero (
Δ
F<0) by PI control,
the target frequency is used as the command frequency.
Dropping function
Input current control, etc.
Upper limit frequency
FMAX
Lower limit frequency
FMIN
Initial frequency
PI control
Defrost control
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...