SiUS092230EA
Troubleshooting for Outdoor Unit
Part 6 Service Diagnosis
179
Troubleshooting
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
YES
Turn off the power.
Check the connection.
Check the power supply voltage.
Correct the power supply.
(R22764)
NO
NO
NO
NO
YES
YES
YES
YES
Check No. 20
Check the short circuit of the
diode bridge.
Check No.15
Check with the inverter analyzer.
Turn off the power. Disconnect the
harnesses U, V, and W.
Turn on the power. Check the
electrolytic capacitor voltage.
Electrical
components or
compressor harnesses
connected as
specified?
Replace the outdoor unit
PCB (main PCB).
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Reconnect the electrical
components or compressor
harnesses as specified.
Replace the outdoor unit
PCB (main PCB).
Inverter analyzer:
RSUK0917C
Normal?
NO
YES
Check No. 18
Check the discharge pressure.
Replace the stop valve.
OK?
Within 320 VDC?
Any LED off?
+ 100
– 50
Is the
power supply
voltage fluctuation within
±10% from the rated
value?
Summary of Contents for RX-W Series
Page 1: ... Applied Models Inverter Pair Heat Pump Service Manual SiUS092230EA Inverter Pair RX W Series ...
Page 207: ...SiUS092230EA Check Part 6 Service Diagnosis 201 15 18 24 class R25105 1 2 3 4 Multimeter ...
Page 209: ...SiUS092230EA Check Part 6 Service Diagnosis 203 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Page 239: ...SiUS092230EA Piping Diagrams Part 8 Appendix 233 RX24WMVJU9 3D141502 ...