Control Specification
SiUS092230EA
84
Part 4 Functions and Control
5.4 Discharge Pipe Temperature Control
Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Details
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
09/12 class
15/18/24 class
(°C)
(°F)
(°C)
(°F)
A
110
230.0
110
230.0
B
103
217.4
103
217.4
C
98
208.4
101.5
214.7
D
93
199.4
100
212.0
E
88
190.4
95
203.0
(R25005)
Discharge pipe
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
E
A
B
C
D