Field Settings for Indoor Unit
SiUS372201EA
207
Part 5 Field Settings and Test Operation
Due to the aforementioned, when the "Auto restart after power failure” setting is ON, be careful for
the following situations that may occur.
1.4.21 Airflow Setting when Cooling Thermostat is OFF
This is used to set airflow to LL airflow when cooling thermostat is OFF.
If the airflow setting when thermostat is OFF is set to 03: OFF, the air in the indoor unit will be
stagnant and suction air thermistor may not detect room temperature correctly, resulting in
problems that thermostat will not be ON easily.
Use optional remote sensor in such conditions, or set the field setting 10 (20)-2 to
03
(only remote
controller thermistor).
: Factory setting
1.4.22 Setting of Airflow Rate
Make the following setting according to the ceiling height. The second code No. is set to
01
at the
factory.
*1. For FXUQ30/36PA, applicable lower than 4.0 m (13 ft).
1. The air conditioner will start operation suddenly after power failure,
or when the main power supply is restored. The user might be surprised
and wonder why the air conditioner turned ON suddenly.
2. During maintenance, if the main power supply is turned OFF while the
units are in operation, the units will automatically start operation
(the fan will rotate) after the power supply is restored due to completion
of the maintenance work.
Caution
Mode
No.
First Code
No.
Second Code
No.
Contents
12 (22)
6
01
LL tap
02
Set fan speed
03
OFF
FXFQ07-24T, FXUQ18/24P, FXUQ18/24PA
: Factory setting
Mode
No.
First Code
No.
Second
Code No.
Contents
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard
Lower than
2.7 m
(8-3/4 ft)
Lower than
3.0 m
(10 ft)
Lower than
3.5 m
(11-1/2 ft)
02
High Ceiling 1
Lower than
3.0 m
(10 ft)
Lower than
3.3 m
(10-3/4 ft)
Lower than
3.8 m
(12-1/2 ft)
03
Higher Ceiling 2
Lower than
3.5 m
(11-1/2 ft)
Lower than
3.5 m
(11-1/2 ft)
—
FXFQ30-48T, FXUQ30/36P, FXUQ30/36PA
: Factory setting
Mode
No.
First Code
No.
Second
Code No.
Contents
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard
Lower than
3.2 m
(10-1/2 ft)
Lower than
3.6 m
(12 ft)
Lower than
4.2 m
(13-3/4 ft)
02
High Ceiling 1
Lower than
3.6 m
(12 ft)
Lower than
4.0 m
(13-1/8 ft)
Lower than
4.2 m
(13-3/4 ft)
03
Higher Ceiling 2
Lower than
4.2 m
(13-3/4 ft) (*1)
Lower than
4.2 m
(13-3/4 ft) (*1)
—
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...