SiUS372201EA
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
240
[2-38]:
Emergency operation “Master”
To disable compressor operation permanently: in case of single module or “Master” unit
of a multi outdoor system, this setting allows:
Default value: 0. Compressor operation enabled.
Field setting:
Set 1: Master INV. 1 is disabled permanently.
Set 2: Master INV. 2 is disabled permanently
Set 3: Master module is disabled permanently.
[2-39]:
Emergency operation “Sub”
To disable compressor operation of “Sub” unit of a multi outdoor system permanently:
Default value: 0. Compressor operation enabled.
Field setting:
Set 1: Sub INV. 1 is disabled permanently.
Set 2: Sub INV. 2 is disabled permanently
Set 3: Sub module is disabled permanently.
[2-42]:
Outdoor fan noise countermeasure
Change fans rotational speed and reduce noise by the interference of air blow noise
between outdoor units.
Default value: 0
Field setting:
Mode A: 1
Mode B: 2
[2-45]:
Low ambient cooling
Default value: 0.
[2-45]
Description
0 (default)
No low ambient cooling available.
1
Low ambient cooling available.
This setting is not applicable to BS-Q54TVJ models.
[2-47]:
Te target temperature during heat recovery operation
Default value: 2.
Value
[2-47]
Te target
0
Auto (6-17°C) (42.8-62.6°F)
2 (default)
6°C (42.8°F)
3
7°C (44.6°F)
4
8°C (46.4°F)
5
9°C (48.2°F)
6
10°C (50.0°F)
7
11°C (51.8°F)
Change [2-47] to 0, 2-7 in function of required operation method during heat recovery operation.
For more information and advice about the effect of these settings, see
Energy Saving and
Optimum Operation
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...