Field Setting from Outdoor Unit
SiUS372201EA
239
Part 5 Field Settings and Test Operation
Note(s)
1. Indoor condition A: Temperature difference Average of (indoor air temperature – set
temperature) is less than 1.5°C (2.7°F).
2. Indoor condition B: Temperature difference Average of (indoor air temperature – set
temperature) is 3°C (5.4°F) or more.
[2-32]:
Forced, all time, power consumption limitation operation (no external control adaptor
is required to perform power consumption limitation)
If the system always needs to run under power consumption limitation conditions,
this setting activates and defines the level power consumption limitation that will be
applied continuously. The level is according to the table.
Default value: 0 (OFF).
Value
[2-32]
Restriction reference
0 (default)
Function not active
1
Follows [2-30] setting
2
Follows [2-31] setting
Change [2-32]: 0,1 or 2 in function of required limitation.
[2-34]:
Indoor fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air
temperature for energy saving
Value
[2-34]
Indoor fan tap setting
0 (default)
Fan speed is limited to L tap when indoor units capacity
130%.
1
In heating mode, fan speed is limited to L tap when indoor units capacity
130%.
2
Fan speed follows the setting of remote controllers (not limited by indoor units
connection capacity).
3
Limited in cooling when Ta < 29.5°C (85.1°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 32.5°C (90.5°F) or Indoor condition is in condition B (
2)
4
Limited in cooling when Ta < 23.5°C (74.3°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 26.5°C (79.7°F) or Indoor condition is in condition B (
2)
5
Limited in cooling when Ta < 19.3°C (66.7°F) and Indoor condition is in condition A
(
1)
Returned when Ta > 22.3°C (72.1°F) or Indoor condition is in condition B (
2)
6
Limited in cooling when Ta < 29.5°C (85.1°F)
Returned when Ta > 32.5°C (90.5°F)
7
Limited in cooling when Ta < 23.5°C (74.3°F)
Returned when Ta > 26.5°C (79.7°F)
8
Limited in cooling when Ta < 19.3°C (66.7°F)
Returned when Ta > 22.3°C (72.1°F)
[2-35]:
Height difference setting
Default value: 1
In case the outdoor unit is installed in the lowest position (indoor units are installed on a
higher position than outdoor units) and the height difference between the highest indoor
unit and the outdoor unit exceeds 40 m (130 ft), the setting [2-35] should be changed to
0.
If the setting [2-35] is changed to 0, continuous heating will not be provided during
defrost of oil return for conditions above ambient temp. 10°C (50°F) and room temp.
24°C (75°F).
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...