SiUS372201EA
Field Setting from Outdoor Unit
Part 5 Field Settings and Test Operation
228
34
Indoor fan tap
setting
Indoor fan speed is limited to L tap
depending on connection capacity
and outdoor air temperature (Ta).
1.Indoor condition A: Temperature
difference average of (indoor air
temperature – set temperature) is
less than 1.5°C (2.7°F).
2.Indoor condition B: Temperature
difference average of (indoor air
temperature – set temperature) is
3°C (5.4°F) or more.
2.
3
4
Indoor capacity ≥ 130%
0
Indoor capacity ≥ 130% in
heating
1
Remote controller setting (Not
limited)
2
Limited in cooling when
Ta < 29.5°C (85.1°F) and
Indoor condition is in condition
A (
1)
Returned when
Ta > 32.5°C (90.5°F) or Indoor
condition is in condition B (
2)
3
Limited in cooling when
Ta < 23.5°C (74.3°F) and
Indoor condition is in condition
A (
1)
Returned when
Ta > 26.5°C (79.7°F) or Indoor
condition is in condition B (
2)
4
Limited in cooling when
Ta < 19.3°C (66.7°F) and
Indoor condition is in condition
A (
1)
Returned when
Ta > 22.3°C (72.1°F) or Indoor
condition is in condition B (
2)
5
Limited in cooling when
Ta < 29.5°C (85.1°F)
Returned when
Ta > 32.5°C (90.5°F)
6
Limited in cooling when
Ta < 23.5°C (74.3°F)
Returned when
Ta > 26.5°C (79.7°F)
7
Limited in cooling when
Ta < 19.3°C (66.7°F)
Returned when
Ta > 22.3°C (72.1°F)
8
35
Outdoor > 40 m
(130 ft) below
indoor
To increase Tc target heating.
2.
3
5
Level > 40 m (130 ft)
Level max. 40 m (130 ft)
Do not use
0
1
~
7
37
Heat pump
lockout 2
Used for heat pump lockout
2.
3
7
OFF
Mode 1
Mode 2
Mode 3
Mode 4
Mode 5
Mode 6
0
1
2
3
4
5
6
38
Emergency
operation
(master)
To prohibit a compressor or
complete in “Master”. Since
module is permanent disabled,
immediately replace the defective
component(s).
2.
3
8
OFF
Master INV. 1 OFF
Master INV. 2 OFF
Master unit OFF
0
1
2
3
39
Emergency
operation (sub)
To prohibit a compressor or
complete “sub 1”. Since module is
permanent disabled, immediately
replace the defective
component(s).
2.
3
9
OFF
Sub INV. 1 OFF
Sub INV. 2 OFF
Sub unit OFF
0
1
2
3
42
Outdoor fan
Outdoor fan noise countermeasure
(limit fan speed).
2.
4
2
Standard
Mode A
Mode B
0
1
2
45
Low ambient
cooling
Low ambient cooling function
setting.
(This setting is not applicable to
BS-Q54TVJ models.)
2.
4
5
Low ambient cooling not
available
Low ambient cooling
available
0
1
No.
1
Item
Description
7 segment
display
Description
7 segment
display
Range
SEG
1
SEG
2
SEG
3
SEG
1
SEG
2
SEG
3
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...