Protection Control
SiUS372201EA
139
Part 4 Functions and Control
6. Protection Control
6.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due to
abnormal increase of high pressure and to protect compressors against the transient increase of
high pressure.
Cooling
Normal control
21-step down
9-step up
9-step down
3-step up
2-step down
1-step up
2-step down
After 10 seconds
After 15 seconds
After 15 seconds
After 10 seconds
Pc > 3.57 MPa
(518 psi)
Pc > 3.70 MPa
(537 psi)
Pc < 3.14 MPa
(455 psi)
Pc < 3.43 MPa
(498 psi)
Pc > 3.67 MPa
(532 psi)
Pc > 3.62 MPa
(525 psi)
Pc > 3.57 MPa
(518 psi)
Compressor step: 1
After 15 seconds
Pc < 3.32 MPa (481 psi)
After 10 seconds
Upper limit compressor step: max (Max. Step)
Pc > 3.72 MPa
(540 psi)
Pc: High pressure sensor
detection value for each
outdoor unit
Current
step
maintained
Abnormal stop
(
E3
is displayed)
High pressure standby
(2 times within 40 minutes)
After 10
seconds
High pressure switch (4.0 MPa
(580 psi)) is activated
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...