Troubleshooting by Error Code
SiUS372201EA
323
Part 6 Service Diagnosis
Note(s)
1. If the filter auto clean operation mode is set to a designated time period, perform a filter auto
clean operation as described below to clear the
AH
error code. (If scheduled operation time is not
set, the filter auto clean operation will be performed automatically after air conditioning operation is
stopped, so the following operation is unnecessary.)
1. On the remote controller, select "Filter Auto Clean" menu. The screen will change into a
cleaning time period setting screen. Confirm the set time period. (Example: 0:00 to 3:00)
2. Select "Clock & Calendar" on the remote controller and set the current time to the time one
minute before the beginning of the time set in step 1. (Example: If the set time is from 0:00 to
3:00, set the current time to 23:59, one minute before 0:00)
3. After about 1 minute, filter auto clean operation will start. (
AH
error cleared)
4. After confirming that the filter auto clean operation is finished, return the time changed in step 2
to the regular time.
NO
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
YES
Stop the air conditioning
operation and perform filter
auto clean operation (
1).
(Please set a time period
during which air conditioning
operation is stopped for about
20 minutes every day.)
Has any air
conditioning operation been
running continuously for
24 hours?
The error could be caused by
other causes. Refer to other
diagnosis flowcharts in the
following order:
AH-03
→
04
→
05
→
06
→
07
→
08.
Check the indoor unit control
PCB and self-cleaning
decoration panel PCB.
AH-09
Filter auto clean operation
start disabled error
Diagnosis Flowchart-7
YES
Stop the air conditioning
operation and perform filter
auto clean operation (
1).
(Please set a time period
during which air conditioning
operation is stopped for about
20 minutes, or set the filter
auto clean operation at a time
when air conditioning
operation is not running.)
Is any air
conditioning operation
running during the set
time period?
NO
NO
NO
YES
Remove the external factor.
Is there any
external factor other than the
error such as noise?
YES
Identify and correct the
problem.
Then stop the air conditioning
operation and perform filter
auto clean operation (
1).
Is there any
operation stop due
to an error?
YES
Deactivate the “Disable Filter
Auto Clean” via the remote
controller setting menu.
Then stop the air conditioning
operation and perform filter
auto clean operation (
1).
Is the filter auto
clean operation set to
“disabled”?
NO
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...