SiUS372201EA
Special Control
Part 4 Functions and Control
150
REYQ192-240AA single system when outside temperature is higher than 0°C (32°F)
Part name
Electric symbol
Function of functional part
Compressor motor
M1C, M2C
135.0 rps + 140.0 rps
Fan motor
M1F, M2F
(Defrosting side)
With high pressure
OFF ↔ Step X/2 ↔ Step X
(Evaporating side)
MAX Step
Electronic expansion valve (Heat exchanger right upper)
Y1E
(Defrosting side)
100%
(Evaporating side)
Superheat control
Electronic expansion valve (Heat exchanger right lower)
Y2E
Electronic expansion valve (Heat exchanger left)
Y5E
Electronic expansion valve (Subcooling heat exchanger)
Y3E
Discharge temperature control
Electronic expansion valve (Receiver gas purge)
Y4E
Liquid recovery control
Electronic expansion valve (Refrigerant cooling IPM)
Y6E
Same as normal control
Electronic expansion valve (Refrigerant cooling air)
Y7E
Solenoid valve (Oil separator oil return)
Y1S, Y2S
ON
Solenoid valve (Liquid shutoff)
Y3S
ON
Solenoid valve (Accumulator oil return)
Y4S
ON
Solenoid valve (Refrigerant adjustment)
Y5S
OFF
Solenoid valve (Injection)
Y6S
ON
Four way valve (Heat exchanger right upper)
Y10S
(Defrosting side)
OFF
(Evaporating side)
ON
Four way valve (Heat exchanger right lower)
Y7S
Four way valve (Heat exchanger left)
Y9S
Four way valve (HP/LP gas pipe)
Y8S
OFF
Solenoid valve (Refrigerant cooling bypass)
Y11S
Same as normal control
Ending condition
A lapse of 8 minutes
Tb > 11°C (51.8°F) continues for 60 seconds or more
OR
Indoor unit actuator
Cooling
Heating
Fan
Thermostat ON unit
Remote controller setting
OFF
Non-operating unit
OFF
OFF
Thermostat OFF unit
Remote controller setting
OFF
Electronic expansion valve
Thermostat ON unit
Normal control
0 pulse
Non-operating unit
0 pulse
0 pulse
Thermostat OFF unit
0 pulse
0 pulse
Branch Selector unit actuator
Normal cooling
Normal simultaneous cooling/heating
Normal heating
Cooling
Heating
Electronic
expansion
valve (EVSC)
Y1E
Thermostat ON
0 pulse
0 pulse
Subcooling degree control
0 pulse
Non-operating
0 pulse
0 pulse
0 pulse
0 pulse
Thermostat OFF
0 pulse
0 pulse
0 pulse
0 pulse
Electronic
expansion
valve (EVH)
Y2E
Thermostat ON
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Non-operating
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Thermostat OFF
6,000 pulse
0 pulse
6,000 pulse
6,000 pulse
Electronic
expansion
valve (EVL)
Y3E
Thermostat ON
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Non-operating
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Thermostat OFF
6,000 pulse
6,000 pulse
0 pulse
0 pulse
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...