Outline of Control (Indoor Unit)
Part 4 Functions and Control
164
Assuming suction temperature has changed from 30°C (86°F) to 18°C (64°F) (F
A):
Suction air thermistor is used for temperatures from 30
C (86
F) to 25
C (77
F) (F
D).
Remote controller thermistor is used for temperatures from 25
C (77
F) to 21
C (70
F) (D
B).
Suction air thermistor is used for temperatures from 21
C (70
F) to 18
C (64
F) (B
A).
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower near
the floor where the occupants are. When controlling by suction air thermistor only, the indoor unit
may therefore be turned off by the thermostat before the lower part of the room reaches the set
temperature. The temperature can be controlled so the lower part of the room where the occupants
are does not become cold by widening the range in which remote controller thermistor can be used
so that suction temperature is higher than the set temperature.
Assuming the set temperature in the figure above is 24°C (75°F), and the suction
temperature has changed from 18°C (64°F) to 28°C (82°F) (A
D):
(This example also assumes there are several other air conditioners, and the suction temperature
changes even when the thermostat sensor is off.)
Suction air thermistor is used for temperatures from 18°C (64°F) to 25°C (77°F) (A
C).
Remote controller thermistor is used for temperatures from 25°C (77°F) to 28°C (82°F) (C
D).
Assuming suction temperature has changed from 28°C (82°F) to 18°C (64°F) (D
A):
Remote controller thermistor is used for temperatures from 28°C (82°F) to 23°C (73°F) (D
B).
Suction air thermistor is used for temperatures from 23°C (73°F) to 18°C (64°F) (B
A).
Range in
w
hich remote controller
thermistor can
b
e
u
sed
Range in
w
hich
s
u
ction air thermistor
can
b
e
u
sed
Differential
S
u
ction air temperat
u
re (TH1)
Set temperat
u
re (Ts)
12
14
16
18
20
22
24
26
28
30
32
34
53.6
57.2
60.8
64.4
68.0
71.6
75.2
78.8
82.4
86.0
89.6
93.2
°
C
°
F
°
C
32
30
28
26
24
22
20
18
16
°
F
89.6
86.0
82.4
78.8
75.2
71.6
68.0
64.4
60.8
TH1 = Ts + 12
≤
33
°
C
TH1 = Ts + 21.6
≤
91.4
°
F
TH1 = Ts + 10
≤
31
°
C
TH1 = Ts + 18
≤
87.8
°
F
TH1 = Ts + 1
≤
31
°
C
TH1 = Ts + 1.8
≤
87.8
°
F
TH1 = Ts – 1
°
C
TH1 = Ts – 1.8
°
F
Summary of Contents for REYQ-AATJA
Page 1: ...Service Manual Heat Recovery 60 Hz REYQ AATJA 208 230 V REYQ AAYDA 460 V SiUS372201EA...
Page 465: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 458 BS6 8Q54TVJ 2D089122B...
Page 466: ...Wiring Diagrams SiUS372201EA 459 Part 7 Appendix BS10 12Q54TVJ 2D089121B...
Page 469: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 462 BSF6 8Q54TVJ 2D123905A...
Page 472: ...Wiring Diagrams SiUS372201EA 465 Part 7 Appendix FXZQ05 07 09 12 15 18TAVJU 3D110443A...
Page 476: ...Wiring Diagrams SiUS372201EA 469 Part 7 Appendix FXEQ07 09 12 15 18 24PVJU 3D098557A...
Page 477: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 470 FXDQ07 09 12 18 24MVJU C 3D050501C...
Page 483: ...SiUS372201EA Wiring Diagrams Part 7 Appendix 476 FXHQ12 24 36MVJU 3D048116C...
Page 484: ...Wiring Diagrams SiUS372201EA 477 Part 7 Appendix FXAQ07 09 12 18 24PVJU 3D075354F...
Page 490: ...Wiring Diagrams SiUS372201EA 483 Part 7 Appendix VAM1200GVJU 3D073270D...